Section 75
00-02-0522
04-06-11 -
41 -
iGUARD Electrical Installation
Electrical Hook up
There are several wire harnesses or wire harness plug-in connectors that may be shipped with
the controller.
Two
(2),
10-position connector
: for J1939, RS485 / RS232
One
(1),
16-position connector
: for Digital Inputs
One
(1),
18-position connector
: for Digital Inputs
One
(1),
24-position connector
: for Analog Inputs
One
(1),
6-position connector
: for Current Transformer Inputs
One
(1),
4-position connector
: for AC Voltage and Neutral Inputs
One
(1),
4-position connector
: for DC supply
Additionally there is a 2-position connector for normally closed Emergency Shutdown switch
that is shipped installed on the controller. There are three (3), 1/4
”
blade-type push-on
terminals for each of the eight (8) form-
C
-relays. They are Normally Open, Normally Closed,
and Common. These contact outputs are dry. The dual row white connectors are all intended
for low voltage.
J1 – Power Connector
J2 – Communications Connector
This communications connector supports J1939 and Modbus server (slave).