e
f
3 times
FLASH
PC 02
Top temperature protection of compressor or High temperature
protection of IPM module or High pressure protection
TS11-S-INV
5 times
FLASH
PC 04
Inverter compressor drive error
TS12-S
1 time
FLASH
PC 08
Current overload protection
TS08-S
6 times
FLASH
PC 40
Communication error between outdoor main chip and compressor
driven chip
TS33
7 times
FLASH
PC 03
Low pressure protection
TS13-INV
1 times
ON
--
Indoor units mode conflict(match with multi outdoor unit)
TS14
For other errors:
The display board may show a garbled code or a code undefined by the service manual. Ensure that this code is not a
temperature reading.
Troubleshooting:
Test the unit using the remote control. If the unit does not respond to the remote, the indoor PCB requires replacement.
If the unit responds, the display board requires replacement.
88 flash frequency:
... ...
Service manual
H11 series
Troubleshooting 4