2. Pipe Length and Drop Height
The length and elevation of connection pipe are shown in the table below. if the pipe length exceeds max pipe length,
additional refrigerant should be charged to ensure nominal cooling/heating capacity.
Capacity(Btu/h)
Standard Length
Max Pipe Length
Max Elevation
Additional Refrigerant
9k/12k
5m (16.4ft)
25m (82.0ft)
10m (32.8ft)
12g/m (0.13oz/ft)
18k
30m(98.4ft)
20m(65.6ft)
24k
24g/m (0.26oz/ft)
If oil flows back into the outdoor unit’s compressor, this might cause liquid compression or deterioration of oil return. Oil
traps in the rising gas pipe can prevent this.
1. Indoor unit is installed higher than outdoor unit
2. Outdoor unit is installed higher than indoor unit
If indoor unit is installed higher than outdoor unit, oil trap should be set every 10m(32.8ft) of vertical distance.
If the outdoor unit is installed higher than the indoor unit, proper oil should return to the compressor along with the
suction of refrigerant to keep lubrication of compressor. If the suction flow velocity drops below 7.62m/s(1500fpm (feet
per minute)), oil won’t return to the compressor. An oil trap should be installed every 6m(20ft) of vertical distance.
e
Specifications 3
f
Service manual
H11 series
Summary of Contents for MUPR-09-H11-E
Page 1: ...Service manual MUPR H11 www mundoclima com CL20055 CL20058 R32...
Page 16: ...Service manual H11 series MUPR 24 H11 I Specifications 7f e...
Page 18: ...Service manual H11 series MUPR 24 H11 E Specifications 9 f e...
Page 59: ...e Outdoor Unit Disassembly 4 f 2 Panel Plate X301 Service manual H11 series MUPR 18 H11 E...
Page 60: ...e Outdoor Unit Disassembly 5 f 3 Panel Plate X401 Service manual H11 series MUPR 24 H11 E...
Page 117: ...Service manual H11 series e f Troubleshooting 25...