Product Features
4
f
3. Basic
Functions
3.1 Abbreviation
Unit element abbreviations
Abbreviation
Element
T1
Indoor room temperature
T2
Coil temperature of evaporator
T3
Coil temperature of condenser
T4
Outdoor ambient temperature
Tsc
Adjusted setting temperature
TP
Compressor discharge temperature
3.2 Fan
Mode
When fan mode is activated:
• The outdoor fan and compressor cease operation.
• Temperature control is disabled and indoor room
temperature is displayed.
• The indoor fan speed can be set to 1%~100%, or
auto.
• The louver operations are identical to those in cooling
mode.
• Auto fan: In fan-only mode, AC operates the same as
auto fan in cooling mode with the temperature set at
24°C.(Tsc =24°C)
3.3 Cooling
Mode
3.3.1 Compressor
Control
Reach the configured temperature:
1) When the compressor runs continuously for within 120
minutes.
• If the following conditions are satisfied, the
compressor ceases operation.
• Calculated frequency(fb) is less than minimum limit
frequency(FminC).
• Compressor runs at FminC more than 10 minutes
• T1 is lower than or equal to (Tsc-CDIFTEMP-0.5°C)
Note: CDIFTEMP is EEPROM setting parameter. It is 2°C
usually.
2) When the compressor runs continuously for more than
120 minutes.
• If the following conditions are satisfied, the
compressor ceases operation.
• Calculated frequency(fb) is less than minimum limit
frequency(FminC).
• Compressor runs at FminC more than 10 minutes.
• T1 is lower than or equal to (Tsc-CDIFTEMP).
Note: CDIFTEMP is EEPROM setting parameter. It is 2°C
usually.
3) If one of the following conditions is satisfied, not judge
protective time.
• Compressor running frequency(fr) is more than test
frequency(TestFre).
• Compressor running frequency is equal to test
frequency, T4 is more than 15°C or T4 fault.
• Change setting temperature.
• Turbo or sleep function on/off
• Various frequency limit shutdown occurs.
3.3.2
Indoor Fan Control
1) In cooling mode, the indoor fan operates continuously.
The fan speed can be set to 1%-100%, or auto.
2) Auto fan
For DC fan motor units:
• Descent curve
• When T1-Tsc is lower than or equal to 3.5°C, fan
speed reduces to 80%;
• When T1-Tsc is lower than or equal to 1°C, fan
speed reduces to 60%;
• When T1-Tsc is lower than or equal to 0.5°C, fan
speed reduces to 40%;
• When T1-Tsc is lower than or equal to 0°C, fan
speed reduces to 20%;
• When T1-Tsc is lower than or equal to -0.5°C, fan
speed reduces to 1%.
• Rise curve
• When T1-Tsc is higher than 0°C, fan speed
increases to 20%;
• When T1-Tsc is higher than 0.5°C, fan speed
increases to 40%;
• When T1-Tsc is higher than 1°C, fan speed
increases to 60%;
• When T1-Tsc is higher than 1.5°C, fan speed
increases to 80%;
• When T1-Tsc is higher than 4°C, fan speed
increases to 100%.
Service manual
H11 series
Summary of Contents for MUPR-09-H11-E
Page 1: ...Service manual MUPR H11 www mundoclima com CL20055 CL20058 R32...
Page 16: ...Service manual H11 series MUPR 24 H11 I Specifications 7f e...
Page 18: ...Service manual H11 series MUPR 24 H11 E Specifications 9 f e...
Page 59: ...e Outdoor Unit Disassembly 4 f 2 Panel Plate X301 Service manual H11 series MUPR 18 H11 E...
Page 60: ...e Outdoor Unit Disassembly 5 f 3 Panel Plate X401 Service manual H11 series MUPR 24 H11 E...
Page 117: ...Service manual H11 series e f Troubleshooting 25...