Information requirements for air-to-air conditioners
Model(s): MVD-V6R335W/V2GN1
Test matching indoor units form2, cassette: 6×MVD-56Q4*
Outdoor side heat exchanger of air conditioner: air
Indoor side heat exchanger of air conditioner: air
Type: compressor driven
Driver of compressor: electric motor
Rated cooling capacity
Seasonal space cooling
energy efficiency
Item
Symbol
P
rated,c
33.5
Value
Unit
Item
Symbol
Value
Unit
kW
Declared cooling capacity for part load at given outdoor
temperatures T
j
and indoor 27/19°C
(
dry/wet bulb
)
s,c
258
%
Declared energy efficiency ratio or gas utilisation efficiency
/auxiliary energy factor for part load at given outdoor
temperatures T
j
T
j
=+35°C
T
j
=+30°C
T
j
=+25°C
T
j
=+20°C
Off mode
Thermosat-off mode
Crankcase heater mode
Standby mode
P
CK
P
SB
P
dc
P
dc
P
dc
P
dc
33.50
24.68
15.87
9.65
kW
kW
kW
kW
kW
kW
kW
kW
T
j
=+35°C
T
j
=+30°C
T
j
=+25°C
T
j
=+20°C
EER
d
EER
d
EER
d
EER
d
3.50
4.72
6.83
14.25
--
--
--
--
Degradation
co-efficient for air
conditioners(*)
C
dc
0.25
--
Power consumption in modes other than "active mode"
P
OFF
P
TO
0.05
0.005
0.005
0.05
Other items
Capacity control
variable
For air-to-air air conditioner:
air flow rate, outdoor
measured
Sound power
level, outdoor
L
WA
81
dB
GWP of the refrigerant
2088
kg CO
2 eq
(100years)
10000
m
3
/h
--
Contact details
(*)If C
dc
is not determined by measurement, then the default degradation coefficient of heat pumps shall be 0.25.
Where information relates to multi-split air conditioners, the test result and performance data may be obtained on the basis
of performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Cooling - Information requirements for air-to-air air conditioners
74