24
Issue 13 (11/14/2017)
factor is 3.9 mV per degree Celsius per cell. This value can be selected in the Configuration Menu.
See section
5.3.5 for an explanation on modifying these settings.
Battery Test
If the Battery Test is not running this screen is displayed.
starts the test,
exits.
If the Battery Test is running this screen is displayed.
stops the test,
exits. If exiting while the test is
running the test will continue to run.
The Battery Test can be stopped from either the keypad, from a remote
command
,
or by the power supply entering standby mode following a
power line failure. In each case this screen will be displayed.
After a Battery Test finishes, another test cannot be started for a
▓▓▓▓
minimum of 30 seconds. During this delay a bargraph ticks down the
remaining time.
5.3.5 Configuration Menu
The Configuration Menu allows for several system performance variables and options to be modified. Use
caution when adjusting these values as system operation can be affected by improper settings.
Battery Test Parameters
The Battery Test can be performed in three ways: manually from the Battery Status menu, remotely via an HMS
data command, or automatically. The duration of individual tests, the frequency of automatic tests, and the
behavior of remote tests are all configurable items.
A test will run for the selected duration unless stopped from the keypad, stopped by a remote command, or
interrupted by the power supply entering standby mode due to power line failure.
The arrow keys increase or decrease the Battery Test Duration
in 1 minute increments from 1 to 60 minutes. Default: 5 minutes.
accepts changes and exits,
discards changes and exits
.
If the Test Frequency is set to OFF automatic tests will not take place, otherwise tests will occur at the selected
interval.
Select the time between automatic battery tests. Arrow keys
choose between OFF, 14 or 28 days. Default: OFF.
accepts changes and exits,
discards changes and exits
.
Selects if Remote Tests are timed by the “Test Duration” setting. If ON,
tests are timed. If OFF, tests run until stopped
manually, they fail, or are
interrupted by power loss. Default: OFF.
accepts changes and
exits,
discards changes and exits
.
Summary of Contents for EB1s
Page 2: ......
Page 35: ...33 Issue 13 11 14 2017 Fig 8 1 Battery Balancer wiring 36V 3 batteries 1 string ...
Page 36: ...34 Issue 13 11 14 2017 Fig 8 2 Battery Balancer wiring 48V 4 batteries 1 string ...
Page 37: ...35 Issue 13 11 14 2017 Fig 8 3 Battery Balancer wiring 36V 6 batteries 2 strings ...
Page 38: ...36 Issue 13 11 14 2017 Fig 8 4 Battery Balancer wiring 48V 8 batteries 2 strings ...