30
Issue 13 (11/14/2017)
7.4 Troubleshooting
The troubleshooting guide has been designed to help you quickly locate and resolve common power supply
problems. If you still cannot solve the problem, replace the power supply with a known good unit.
Condition
Check
No output to load
Batteries connected
AC line power present
Output connector plugged in
Battery voltage within limits
AC utility voltage present and within limits
Incorrect output voltage
Batteries connected
AC line power present
Check output voltage and current displays.
Check output connector and connections to cable plant.
Batteries will not charge
Batteries connected
AC line power present
Battery breaker tripped
Battery terminals and connectors
Battery failure
Batteries not properly charged
Batteries connected
AC line power present
Verify connection of battery cable
Verify charger mode at front panel
Measure charge voltage (Bulk, Equalize, Float)
Alarm Conditions
Major Alarms:
Cause
Corrective action
Configuration Fault
System configuration does not match detected operating conditions
Contact Multilink
Inverter Fault
System has detected that the inverter current is too high
Remove cause of overcurrent, restart UPS,
replace inverter if damaged
Sleep Mode Fault
In standby, batteries have discharged to the shutdown value
Restore line voltage, charge batteries
High Line Voltage
System has detected that the Line Voltage exceeds specifications
Remove cause of overvoltage
Battery Test Fail
In Test Mode, batteries have discharged to the shutdown value
Recharge or replace batteries
Inverter Overtemp
Inverter temperature exceeds 90°C
Place unit in environment that meets factory
specifications, replace UPS if damaged
Out 1 Over Current
Output 1 current has exceeded setpoint by more than 1A
Reduce load
Out 2 Over Current
Output 2 current has exceeded setpoint by more than 1A
Reduce load
Missing Batteries
System has detected that the battery string is disconnected
Reconnect batteries
Low Battery Voltage
System has detected that the battery string voltage is too low
Recharge or replace batteries
High Battery Voltage
System has detected that the battery string voltage is too high
Check batteries, replace inverter if damaged
Out 1 Short Circuit
A short circuit has been detected on output 1
Reduce load, check for short circuit
Out 2 Short Circuit
A short circuit has been detected on output 2
Reduce load, check for short circuit
Out 1 Fault Disable
Optional Smart Breaker has shutdown output 1
Reduce load, check for short circuit, clear
fault
Out 2 Fault Disable
Optional Smart Breaker has shutdown output 2
Reduce load, check for short circuit, clear
fault
Minor Alarms:
Cause
Corrective action
No Temperature Probe
Battery temperature probe is disconnected or inoperative
Connect or replace temperature probe
Line Voltage Fail
Utility line voltage has failed and power supply is in standby
Restore utility line voltage
Out 1 Over Current
Output 1 current has exceeded setpoint by less than 1A
Reduce load
Out 2 Over Current
Output 2 current has exceeded setpoint by less than 1A
Reduce load
Global Over Current
Total output current has exceeded setpoint
Reduce load
Inverter Overtemp
Inverter temperature exceeds 75°C but is less than 90°C
Monitor condition
Summary of Contents for EB1s
Page 2: ......
Page 35: ...33 Issue 13 11 14 2017 Fig 8 1 Battery Balancer wiring 36V 3 batteries 1 string ...
Page 36: ...34 Issue 13 11 14 2017 Fig 8 2 Battery Balancer wiring 48V 4 batteries 1 string ...
Page 37: ...35 Issue 13 11 14 2017 Fig 8 3 Battery Balancer wiring 36V 6 batteries 2 strings ...
Page 38: ...36 Issue 13 11 14 2017 Fig 8 4 Battery Balancer wiring 48V 8 batteries 2 strings ...