683 – AL PhyA Red
Red alarm
Associated parameter 1.4570.091
Cause
Corrective action
An internal combined alarm at
step motor A was detected
u
An exact fault designation is transmitted via CAN bus to the
genset control system
684 – AL PhyB Red
Red alarm
Associated parameter 1.4570.191
Cause
Corrective action
An internal combined alarm at
step motor B was detected
u
An exact fault designation is transmitted via CAN bus to the
genset control system
685 – AL Lube Oil Min
Red alarm
Associated parameter 1.1480.307
Cause
Corrective action
Minimum engine oil filling level
detected.
1. Check engine oil level (→ Page 150).
2. Check replenishment system.
3. Fill oil.
686 – AL Lube Oil Max
Red alarm
Associated parameter 1.1480.309
Cause
Corrective action
Maximum engine oil filling level
detected.
1. Check engine oil level (→ Page 150).
2. Check replenishment system.
3. Drain oil.
688 – LO Oil Refill
Yellow alarm
Associated parameter 1.1480.301
Cause
Corrective action
No oil replenishment within a
configurable time.
u
Check oil replenishment system.
689 – HI Oil Refill
Yellow alarm
Associated parameter 1.1480.303
Cause
Corrective action
Engine oil was refilled too often
within a certain time interval.
u
Check engine oil level (→ Page 150). Check oil supply.
MS150097/01E 2013-10
| Troubleshooting | 123
TIM-ID: 0000027858 - 001