1.4550.036 – A - Temperature derating active
Yellow alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
The internal temperature is
higher than the limit.
1. Check temperature in room. Restart ProAct.
2. Restart ProAct.
1.4550.037 – A - Temperature above 120 °C
Red alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
The internal temperature is
higher than the limit.
1. Check temperature in room. Restart ProAct.
2. Restart ProAct.
1.4550.038 – A - Loss of Position Demand
Red alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
Position specification missing or
is outside the range
1. Check setting.
2. Check cabling.
1.4550.039 – A - Demand Tracking Fault
Yellow alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
ProAct setting is incorrect.
u
Check setting.
1.4550.040 – A - Analog Position Demand Failed
Yellow alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
ProAct setting is incorrect.
u
Check setting.
1.4550.041 – A - PWM Position Demand Failed
Yellow alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
ProAct setting is incorrect.
u
Check setting.
1.4550.042 – A - CAN Position Demand Failed
Red alarm. Initiated by ProAct A-Bank.
Cause
Corrective action
Position specification not
received or received too late
u
Check cabling and setting.