Remedy the cause, re-enable starting
Item
Action
Engine Control System
Determine cause of emergency stop and take remedial action; contact Serv-
ice if the fault cannot be corrected.
Fault acknowledgment is possible in engine stop mode only . Automatic se-
lection and remote start immediately following an emergency engine stop is
not admissible.
Plant control system
An extended scavenging phase with the ignition off precedes engine starting
when selected again following an emergency engine stop. Suitable exhaust
gas ventilation equipment must be provided in the facility to ensure that the
exhaust gas system downstream of the engine is safely purged.
• A contact is provided to request the ventilation system in the scavenging
phase.
Note:
Gas train
• The gas control system must be equipped with an SAV (safety shut-off
valve) when using gas control systems with inlet pressures in excess of
0.1 bar. If the SAV is tripped by an EMERGENCY STOP it must be reset
manually. SAV tripping is not indicated by the engine.
Table 36: Remedy the cause, re-enable starting
46 | Operation | MS150114/01E 2015-03
TIM-ID: 0000043159 - 002