112516 – HIHI T-Exhaust B6
Red alarm. Initiated by EMU.
Cause
Corrective action
The exhaust temperature of this
cylinder is too high as compared
with the average value.
1. Check emission values.
2. Check ignition timing (→ Page 141).
3. Check valve drive (exhaust valves do not close).
112517 – HIHI T-Exhaust B7
Red alarm. Initiated by EMU.
Cause
Corrective action
The exhaust temperature of this
cylinder is too high as compared
with the average value.
1. Check emission values.
2. Check ignition timing (→ Page 141).
3. Check valve drive (exhaust valves do not close).
112518 – HIHI T-Exhaust B8
Red alarm. Initiated by EMU.
Cause
Corrective action
The exhaust temperature of this
cylinder is too high as compared
with the average value.
1. Check emission values.
2. Check ignition timing (→ Page 141).
3. Check valve drive (exhaust valves do not close).
112519 – HIHI T-Exhaust B9
Red alarm. Initiated by EMU.
Cause
Corrective action
The exhaust temperature of this
cylinder is too high as compared
with the average value.
1. Check emission values.
2. Check ignition timing (→ Page 141).
3. Check valve drive (exhaust valves do not close).
112520 – HIHI T-Exhaust B10
Red alarm. Initiated by EMU.
Cause
Corrective action
The exhaust temperature of this
cylinder is too high as compared
with the average value.
1. Check emission values.
2. Check ignition timing (→ Page 141).
3. Check valve drive (exhaust valves do not close).
112601 – LOLO T-Exhaust A1
Red alarm. Initiated by EMU.
Cause
Corrective action
The exhaust temperature of this
cylinder is too low as compared
with the average value.
1. Check spark plug.
2. Check emission values.
3. Check ignition timing (→ Page 141).
4. Check valve drive.
MS150114/01E 2015-03
| Troubleshooting | 63
TIM-ID: 0000038611 - 002