TAEevo M05-M10
15
MAINTENANCE AND OPERATING MANUAL
The data inside this manual are not binding and they can be modified by the manufacturer without notice.
All rights reserved.
7.8.4 Fans
7.8.5 Parameters relative to alarms management
dFd
Temperature
displayed during
defrosting phase
Serves to set temperature display
•
rt= real temperature
•
it= defrost start temperature
•
set= set-point
•
dEF= message “dEF”
dEF
dAd
Max display
delay after
defrost
Establishes the maximum time interval between the defrost
end and the restoration of the cold store temperature display
0
120
min
30
Fdt
Drip time
Time interval between defrost end temperature and the start of
normal operation.
0
120
min
2
dPO
First defrost after
start
Establishes the defrost function start mode
•
y= immediate
•
n= after time interval ldF
n
dAF
Delay on defrost
after freezing
Time interval between freezing procedure end and the next
associated defrost cycle
0
23h
50min
min
0
Parameter
Description
Min.
Max.
U.M.
Factory
settings
FnC
Fans operating
mode.
Serves to set the fans operating mode.
•
C-n= in parallel with the compressor; off in
defrost phase
•
o-n= continuous, off in defrost phase
•
C-Y= in parallel with compressor; on in
defrost phase
•
o-Y= continuous, on in defrost phase
C-n
Fnd
Start delay after
defrost
Time interval between defrost end and fans start.
0
255
min
0
Fct
Temperature
differential
If the temperature difference between the evaporator probe
and the cold store probe is higher than the value set in Fct, the
fans always run
0
59
0
FSt
Fans stop
temperature
If temperature detected by the evaporator probe is higher than
“FSt” the fans are stopped
-50
50
°C
0
Fon
Fans start time
with compressor
off
With the compressor off, if the temperature conditions are
present, the fans are activated cyclically according to the times
set in Fon and FoF. With Fon= 0 and FoF
N
0 the fans are
always off, with Fon= 0 and FoF= 0 the fans are always off.
0
15
min
0
FoF
Fan stop time
with compressor
off
With the compressor off, if the temperature conditions are
present, the fans are activated cyclically according to the times
set in Fon and FoF. With FoF= 0 and Fon
N
0 the fans are
always on, with Fon= 0 and FoF= 0 the fans are always off.
0
15
min
0
Parameter
Description
Min.
Max.
U.M.
Factory
settings
ALC
Temperature
alarms
configuration
Serves set temperature alarms on the basis of:
•
Ab= absolute temperature (in relation to
parameters ALL and ALU)
•
rE= relative to the SET (in relation to
“SET+ALU” or “SET-ALL” value settings)
Ab
ALU
High temperature
alarm
When this temperature is reached the alarm is signalled
ALL
110
°C
40
ALL
Low temperature
alarm
When this temperature is reached the alarm is signalled
-50,0
ALU
°C
3
Table 5
P
ARAMETERS
RELATIVE
TO
ALARMS
MANAGEMENT
Parameter
Description
Min.
Max.
U.M.
Factory
settings