MrHeater MHU200NG Operating Instructions And Owner'S Manual Download Page 9

Large Unit Heater

9

Operating Instructions and Owner’s Manual

Venting Through Combustible Roof or Wall

FIGURE 6

Listed Thimble

Roof Flashing

Specified 
Terminal

For vertical vent termination, the venting must comply with all the 

General Venting Requirements

 and with the following vent locations 

and clearances:

•  Separate air intake duct from vent pipe by a minimum of 4 feet by 

placing vent pipes higher than adjacent air intake ducts.

•  Utilize a listed type B vent termination cap.

•  The vent terminal must extend a minimum of 2 feet above the roof.

•  Vent caps should be located a minimum of 2 feet away from 

adjoining structures.

•  All vertically vented heaters that are Category I must be connected 

to a chimney or vent complying with a recognized Standard, or 
lined masonry (or concrete) chimney with a material acceptable to 
the authority having jurisdiction. Venting into an unlined masonry 
chimney is not permitted. Refer to the National Fuel Gas Code.

•  Use a listed vent terminal to reduce down drafts and moisture in the 

vent.

•  Ensure the vent connector runs as short as possible with a minimum 

number of elbows. Refer to the (American) National Fuel Gas Code 
ANSI Z223.1 or (Canada) CSA B149.1 Natural Gas and Propane 
Installation Code for maximum vent and vent connector lengths. 
Horizontal run of the vent connector from the induced draft blower 
to the chimney/vent cannot exceed the values in Table 4.

•  When the length of a single wall vent including elbows, exceeds 5 

feet (1.5m), the vent shall be insulated along its entire length with a 
minimum of 1/2” thick foil faced fiberglass 1-1/2# density insulation. 
If a single wall vent is used in an unheated area it shall be insulated. 
Failure to do so will result in condensation of flue gases.

•  All vertical type B-1 vents, single wall vents, or listed chimney lining 

system must be terminated with a listed vent cap or listed roof 
assembly.

•  The vent must extend at least 3’ (1m) above the highest point 

where it passes through a roof of a building and at least 2’ (0.6m) 
higher than any part of a building within a horizontal distance of 
10’ (3.05m) unless otherwise specified by the (American) National 

Fuel Gas Code, ANSI Z223.1 or (Canada) CAN/CGA-B149 Installation 
Code. The vent must extend at least 5’ (1.6m) above the highest 
connected equipment flue collar.

HORIZONTAL VENTING

An appliance that operates with a positive vent static pressure 
and with a vent gas temperature that avoids excessive condensate 
production in the vent is said to be ‘Category III’. This unit heater is 
considered a Category III appliance if the venting system meets all of 
the following criteria:

• 

The vent system terminates horizontally (sideways).

• 

The vent terminates vertically, but the length of the horizontal 
portion of the vent run exceeds 75% of the vertical rise length. 
(e.g.- If the vertical vent height is 10 feet, the horizontal run is 
greater than 7-1/2 feet).

• 

Horizontal venting sections of the vent pipe must be installed with 
a downward slope from the appliance at a pitch of 1/4 inch per 
foot.

• 

The vent terminates below 5 feet of the vent connection on the 
unit.

Due to changes to Z83-8 2009 CSA2.6-2009, the use of single wall 
B-Vent is no longer permitted as an acceptable material when venting 
horizontally, this change covers both residential and commercial 
installations. All horizontally vented units manufactured after July of 
2011 must be vented as a Category III Unit/Utility Heater in compliance 
with UL 1738 & ULS636.

Seal vent pipes with high temperature sealant and three (3) #8 sheet 
metal screws. Vent enclosed spaces and buildings according to the 
guidelines in this manual and applicable national, state, provincial and 
local codes.

You must use venting approved for Category III applications, and 
manufactured by a listed vent system manufacturer. For single wall 
vent systems, one continuous section of double wall vent pipe may be 
used with the vent system to pass through a wall or barrier.

All horizontal Category III vents must be terminated with a listed vent 
cap.

Exhaust Vent Construction Through 

Combustible Walls

FIGURE 7

Fiber Glass 
Insulation 
Min. 2”

Vent Termination 
Support Bracket 
(where required)

Metal 
Sleeve

Metal 
Sleeve

Vent Pipe 
Diameter

Metal Face 
Plate

2” Min.

12” Min.

Terminal

2” Min.

Summary of Contents for MHU200NG

Page 1: ...o this manual For assistance or additional information consult a qualified installer service agency or the gas supplier WHAT TO DO IF YOU SMELL GAS DO NOT try to light appliance DO NOT touch any elect...

Page 2: ...E INSTRUCTIONS BEFORE YOU OPERATE THIS HEATER WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Be sure to read and und...

Page 3: ...perly Set ________________________________ Furnace BTU input _____________________________________ Level ___________________________________________________ Line Pressure _____________________________...

Page 4: ...al Standard Institute Inc 11 West 42nd Street New York NY 10036 These units are CSA International design certified These unit heaters are certified for installation to combustible material as listed i...

Page 5: ...nual is to provide information regarding safety design guidelines installation operation and maintenance of the this gas fired unit heater You must read and understand the instructions and all safety...

Page 6: ...tion of these units must comply with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition and other applicable local building codes In Canada the installation of these units must comply with...

Page 7: ...ontal pitch as directed in these instructions and the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 or CSA B149 1 Installation Code Determine that there is not blockage restriction...

Page 8: ...h a diameter 4 inches greater than the vent pipe diameter must be used If there is 6 feet or more of vent pipe prior to passing through the combustible wall or floor then the metal thimble need only b...

Page 9: ...than any part of a building within a horizontal distance of 10 3 05m unless otherwise specified by the American National Fuel Gas Code ANSI Z223 1 or Canada CAN CGA B149 Installation Code The vent mu...

Page 10: ...ombustion which can result in the production of excessive carbon monoxide Follow these guidelines and all applicable codes for all models prior to installing the combustion air duct work WARNING Suffi...

Page 11: ...drip leg should be installed in the vertical pipe run to the unit In some localities codes may require that a manual main shutoff valve and union furnished by installer be installed external to the un...

Page 12: ...putting into service For leak testing on pressures below 20 inches W C Before leak testing close the field installed manual shut off valve shown on Figure 9 on the supply line to isolate the gas valve...

Page 13: ...ssure Input Rating W C kPa BTU Hr W W C kPa BTU Hr W MHU200NG 7 23 1 8 200 000 58 614 6 66 1 66 192 000 56 269 MHU250NG 7 23 1 8 250 000 73 268 6 66 1 66 240 000 70 337 MHU300NG 3 81 0 95 300 000 87 9...

Page 14: ...the side access control compartment of the unit The low voltage thermostat and accessory control devices can be wired to the terminals in the side access control compartment Refer to the wiring diagra...

Page 15: ...Large Unit Heater 15 Operating Instructions and Owner s Manual Main Components FIGURE 10 Line Voltage Thermostat Wiring Connector on Heater S1 S4 M1 VG MC FS S2 S3 S2 CB SE T1 RFC CFC...

Page 16: ...Large Unit Heater 16 Operating Instructions and Owner s Manual Internal Wiring Diagram FIGURE 11...

Page 17: ...field supplied power wires so that they do not come in contact with the flue wrapper or venter housing These hot surfaces may damage the wire s insulation resulting in damage to the unit THERMOSTAT LO...

Page 18: ...puts set it to the maximum rating 7 Observe the pressure rating on the pressure gauge Verify maximum inlet gas supply pressure 8 Turn off all other gas appliances on the same supply line 9 Observe the...

Page 19: ...manifold pressure hose connector using a soap solution or equivalent method as described in ANSI Z223 1 NFPA 54 Prior to Leaving Job Site Prior to leaving the job site verify that Service access door...

Page 20: ...hts burner DO NOT attempt to light the burners manually 5 There is a main shut off valve upstream of the unit Open it See Figure 9 on Page 11 6 Wait five minutes to clear out any gas If you then smell...

Page 21: ...upply Follow lighting instructions to light unit Check burner flame FLUE PASSAGEWAY AND FLUE BOX The flue passages and flue box should be inspected and cleaned prior to each heating season The sequenc...

Page 22: ...old Screws FUEL CONVERSION INSTRUCTIONS FIGURE 15 Rotation of the Valve Manifold Assembly ROTATE valve manifold assembly The heater is standard manufactured for operation with natural gas In case of u...

Page 23: ...NOT FOLLOWED EXACTLY A FIRE EXPLOSION OR PRODUCTION OF CARBON MONOXIDE MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE THE QUALIFIED SERVICE AGENCY PERFORMING THIS WORK ASSUMES RES...

Page 24: ...space tightly sealed building 1 Remove obstruction or correct vent lengths 2 Replace wiring or hose connections 3 Replace pressure switch The control board does not send spark to the electrode 1 The e...

Page 25: ...ontrol board does not send 120 VAC to the air movement fan after approx 30 seconds after ignition and if contact relay fan control is open and there isn t 24VAC on relay fan control 3 The control boar...

Page 26: ...er listed on the unit rating plate Mr Heater Large Unit Heater Model MHU200NG MHU250NG MHU300NG MHU400NG Liquid Propane to Natural Gas Conversion Kit MHU200NG F260165 MHU250NG F260166 MHU300NG F260167...

Page 27: ...60291 60291 60291 60291 20 BLOWER DRIVE RELAY 60292 60292 60292 60292 21 PRESSURE SWITCH 60293 60294 60294 60294 22 DETECTION ELECTRODE 60295 60295 60295 60295 23 MANUAL RESET SAFETY THERMOSTAT 140 C...

Page 28: ...001 Address any Warranty Claims to the Service Department Mr Heater Inc 4560 W 160TH ST CLEVELAND OHIO 44135 Include your name address and telephone number and include de tails concerning the claim Al...

Reviews: