MrHeater MHU200NG Operating Instructions And Owner'S Manual Download Page 21

Large Unit Heater

21

Operating Instructions and Owner’s Manual

MAINTENANCE

 

CAUTION: Turn off gas and electrical power to unit before 

performing any maintenance or service operations on this 
unit. Remember to follow lighting instructions when putting 
unit back into operation after service or maintenance.

 

If any of the original wire as supplied with the appliance 
must be replaced, it must be replaced with wiring material 
having a temperature rating of at least 105°C.

 

Do not use this appliance if any part has been under water. 
Immediately call a qualified service technician to inspect the 
appliance and replace any gas control which has been under 
water.

 

• 

Check gas tightness of the safety shut off valves on at least an 
annual basis.

• 

To check gas tightness of the safety shut off valves, turn off the 
manual valve upstream of the appliance combination control. 
Remove the hex head plug on the inlet side of the combination 
control and connect a manometer to that tapping.

• 

Turn the manual valve ON to apply pressure to the combination 
control. Note the pressure reading on the manometer, then turn 
the valve off. Any loss of pressure indicates a leak. If a leak is 
detected, use a soap solution to check all threaded connections. 
If no leak is found, combination control is faulty and must be 
replaced before putting appliance back in service.

Should maintenance be required, perform the following inspection and 
service routine:

BURNERS

•  Periodically examine burner flames for proper appearance during the 

heating season. 

•  Before each heating season examine the burners for any deposits or 

blockage that may have occurred.

Clean burners as follows:
1. Turn off both electrical and gas supplies to unit.
2. Disconnect gas supply piping, high tension and sensor leads. 

Remove gas manifold. Remove burner tray.

3. Clean burners as necessary. Make sure that burner heads line up 

properly to ensure flame crossover.  Check spark gap on electrode 
and adjust if required. The gap should be between 0.110 inch and 
0.140 inch (2.79mm to 3.56mm). The gap may be checked with 
appropriately sized twist drills or feeler gauges.

4. Reinstall burner tray, gas manifold, high tension and sensor leads. 

Reconnect gas supply piping.

5. Restore electrical power and gas supply. Follow lighting instructions 

to light unit. Check burner flame.

FLUE PASSAGEWAY AND FLUE BOX

The flue passages and flue box should be inspected and cleaned 
prior to each heating season. The sequence of operation should be as 
follows:

1. Turn off both electrical and gas supply to unit.

2. Disconnect combustion air blower wiring.

3. Remove screws securing flue box to unit. Remove flue box. If 

necessary, remove blower assembly from flue box. Clean flue box 
with wire brush.

4. Remove turbulator retention bracket and turbulators. Clean 

turbulators with wire brush.

5. Remove burners as described in section “BURNERS” section.

6. Clean tubes with a wire brush.

7. Reassemble unit. The combustion air and flue box gaskets should 

also be replaced during reassembly.

8. Restore electrical power and gas supply. Follow lighting instructions 

to light unit. Check operation of unit.

COMBUSTION AIR BLOWER

Under normal operating conditions, the combustion air blower should 
be checked and cleaned prior to the heating season with the power 
supply disconnected. Use a small brush to clean blower wheel.

ELECTRICAL

1. Check all wiring for loose connections.

2. Check for correct voltage at unit (unit operating).

3. Check amperage draw.

FLUE AND CHIMNEY

Check all vent and vent connector joints for tightness. Ensure that 
connections are sealed and that there are no blockages.

OTHER CHECKS

1. Inspect the area near the unit to be sure that there is no 

combustible material located within the minimum clearance 
requirements listed in this manual. Under no circumstances should 
combustible material be located within the clearances specified 
in this manual. Failure to provide proper clearance could result in 
personal injury or equipment damage from fire.

2. Complete the appropriate unit startup procedure as given in the 

Operation section of this Manual (see lighting instructions on the 
unit rating plate.)

• 

Check the burner adjustment.

• 

Also check all gas control valves and pipe connections for leaks.

3. Check the operation of the automatic gas valve by lowering the 

setting of the thermostat, stopping the operation of the gas unit 
heater. The gas valve should close tightly, completely extinguishing 
the flame on the burner.

4. If combustion air is room supplied, ensure that a 12 inch clearance is 

maintained all around the inlet openings.

5. Check and test functions of all safety devices supplied with the 

heater (see UNIT START-UP and UNIT WORKING SEQUENCE 
sections).

Summary of Contents for MHU200NG

Page 1: ...o this manual For assistance or additional information consult a qualified installer service agency or the gas supplier WHAT TO DO IF YOU SMELL GAS DO NOT try to light appliance DO NOT touch any elect...

Page 2: ...E INSTRUCTIONS BEFORE YOU OPERATE THIS HEATER WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Be sure to read and und...

Page 3: ...perly Set ________________________________ Furnace BTU input _____________________________________ Level ___________________________________________________ Line Pressure _____________________________...

Page 4: ...al Standard Institute Inc 11 West 42nd Street New York NY 10036 These units are CSA International design certified These unit heaters are certified for installation to combustible material as listed i...

Page 5: ...nual is to provide information regarding safety design guidelines installation operation and maintenance of the this gas fired unit heater You must read and understand the instructions and all safety...

Page 6: ...tion of these units must comply with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition and other applicable local building codes In Canada the installation of these units must comply with...

Page 7: ...ontal pitch as directed in these instructions and the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 or CSA B149 1 Installation Code Determine that there is not blockage restriction...

Page 8: ...h a diameter 4 inches greater than the vent pipe diameter must be used If there is 6 feet or more of vent pipe prior to passing through the combustible wall or floor then the metal thimble need only b...

Page 9: ...than any part of a building within a horizontal distance of 10 3 05m unless otherwise specified by the American National Fuel Gas Code ANSI Z223 1 or Canada CAN CGA B149 Installation Code The vent mu...

Page 10: ...ombustion which can result in the production of excessive carbon monoxide Follow these guidelines and all applicable codes for all models prior to installing the combustion air duct work WARNING Suffi...

Page 11: ...drip leg should be installed in the vertical pipe run to the unit In some localities codes may require that a manual main shutoff valve and union furnished by installer be installed external to the un...

Page 12: ...putting into service For leak testing on pressures below 20 inches W C Before leak testing close the field installed manual shut off valve shown on Figure 9 on the supply line to isolate the gas valve...

Page 13: ...ssure Input Rating W C kPa BTU Hr W W C kPa BTU Hr W MHU200NG 7 23 1 8 200 000 58 614 6 66 1 66 192 000 56 269 MHU250NG 7 23 1 8 250 000 73 268 6 66 1 66 240 000 70 337 MHU300NG 3 81 0 95 300 000 87 9...

Page 14: ...the side access control compartment of the unit The low voltage thermostat and accessory control devices can be wired to the terminals in the side access control compartment Refer to the wiring diagra...

Page 15: ...Large Unit Heater 15 Operating Instructions and Owner s Manual Main Components FIGURE 10 Line Voltage Thermostat Wiring Connector on Heater S1 S4 M1 VG MC FS S2 S3 S2 CB SE T1 RFC CFC...

Page 16: ...Large Unit Heater 16 Operating Instructions and Owner s Manual Internal Wiring Diagram FIGURE 11...

Page 17: ...field supplied power wires so that they do not come in contact with the flue wrapper or venter housing These hot surfaces may damage the wire s insulation resulting in damage to the unit THERMOSTAT LO...

Page 18: ...puts set it to the maximum rating 7 Observe the pressure rating on the pressure gauge Verify maximum inlet gas supply pressure 8 Turn off all other gas appliances on the same supply line 9 Observe the...

Page 19: ...manifold pressure hose connector using a soap solution or equivalent method as described in ANSI Z223 1 NFPA 54 Prior to Leaving Job Site Prior to leaving the job site verify that Service access door...

Page 20: ...hts burner DO NOT attempt to light the burners manually 5 There is a main shut off valve upstream of the unit Open it See Figure 9 on Page 11 6 Wait five minutes to clear out any gas If you then smell...

Page 21: ...upply Follow lighting instructions to light unit Check burner flame FLUE PASSAGEWAY AND FLUE BOX The flue passages and flue box should be inspected and cleaned prior to each heating season The sequenc...

Page 22: ...old Screws FUEL CONVERSION INSTRUCTIONS FIGURE 15 Rotation of the Valve Manifold Assembly ROTATE valve manifold assembly The heater is standard manufactured for operation with natural gas In case of u...

Page 23: ...NOT FOLLOWED EXACTLY A FIRE EXPLOSION OR PRODUCTION OF CARBON MONOXIDE MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE THE QUALIFIED SERVICE AGENCY PERFORMING THIS WORK ASSUMES RES...

Page 24: ...space tightly sealed building 1 Remove obstruction or correct vent lengths 2 Replace wiring or hose connections 3 Replace pressure switch The control board does not send spark to the electrode 1 The e...

Page 25: ...ontrol board does not send 120 VAC to the air movement fan after approx 30 seconds after ignition and if contact relay fan control is open and there isn t 24VAC on relay fan control 3 The control boar...

Page 26: ...er listed on the unit rating plate Mr Heater Large Unit Heater Model MHU200NG MHU250NG MHU300NG MHU400NG Liquid Propane to Natural Gas Conversion Kit MHU200NG F260165 MHU250NG F260166 MHU300NG F260167...

Page 27: ...60291 60291 60291 60291 20 BLOWER DRIVE RELAY 60292 60292 60292 60292 21 PRESSURE SWITCH 60293 60294 60294 60294 22 DETECTION ELECTRODE 60295 60295 60295 60295 23 MANUAL RESET SAFETY THERMOSTAT 140 C...

Page 28: ...001 Address any Warranty Claims to the Service Department Mr Heater Inc 4560 W 160TH ST CLEVELAND OHIO 44135 Include your name address and telephone number and include de tails concerning the claim Al...

Reviews: