MrHeater MHU200NG Operating Instructions And Owner'S Manual Download Page 3

Large Unit Heater

3

Operating Instructions and Owner’s Manual

START-UP AND PERFORMANCE CHECK LIST

Job Name: ___________________________ Job No.: _____________________________ Date:  _______________________________
Job Location: _________________________ City: ________________________________ State/Province:  _______________________
Installer: _____________________________ City: ________________________________ State/Province:  _______________________
Unit Model No.: _______________________ Serial No.: ____________________________ Service Technician:  ____________________
Electrical Connections Tight? _____________________________ Flue Connections Tight? _____________________________________
Supply Voltage ________________________________________ Fan Timer Operation Checked? _______________________________
Gas Piping Connections Tight & Leak-Tested? _______________ THERMOSTAT Calibrated? ___________________________________
Motor Amps __________________________________________ Heat Anticipator Properly Set? ________________________________
Furnace BTU input _____________________________________ Level?  ___________________________________________________
Line Pressure  _________________________________________
Manifold Pressure W.C. _________________________________

PRODUCT SPECIFICATIONS

This unit heater is a single input warm air heater with an average thermal efficiency of 80%. All units are to be supplied with single-phase 60 Hz 
120VAC power. For specific information on each model, see 

Table 1

.

TABLE 1: Specifications

TABLE 2: General Performance Data

Dimensional Data

FIGURE 1

Top View

Rear View

Width

Height

Length

Width

BTU input

BTU output

Size

[BTU/HR]

[BTU/HR]

WIDTH

LENGTH

HEIGHT

WEIGHT[Lbs.]

MHU200NG

200,000

160,000

41.3”

28.7”

24.8”

175

MHU250NG

250,000

200,000

41.3”

28.7”

24.8”

180

MHU300NG

300,000

240,000

41.3”

28.7”

30.3”

227

MHU400NG

400,000

320,000

41.3”

28.7”

38.6”

280

BTU input

[BTU/HR]

Entering 

Airflow

[CFM]

Outlet 

Velocity

[FPM]

AIr Temp.

Rise [

º

F]

Motor

[Watt]

Motor
[RPM]

Fan Diameter

[Inch.]

MHU200NG

200,000

3,377

960

45.0

650

1,500

21.7

MHU250NG

250,000

3,435

976

55.3

650

1,500

21.7

MHU300NG

300,000

4,507

1,040

50.6

1,000

1,560

24.8

MHU400NG

400,000

5,763

1,040

52.7

1,000

1,560

24.8

Summary of Contents for MHU200NG

Page 1: ...o this manual For assistance or additional information consult a qualified installer service agency or the gas supplier WHAT TO DO IF YOU SMELL GAS DO NOT try to light appliance DO NOT touch any elect...

Page 2: ...E INSTRUCTIONS BEFORE YOU OPERATE THIS HEATER WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Be sure to read and und...

Page 3: ...perly Set ________________________________ Furnace BTU input _____________________________________ Level ___________________________________________________ Line Pressure _____________________________...

Page 4: ...al Standard Institute Inc 11 West 42nd Street New York NY 10036 These units are CSA International design certified These unit heaters are certified for installation to combustible material as listed i...

Page 5: ...nual is to provide information regarding safety design guidelines installation operation and maintenance of the this gas fired unit heater You must read and understand the instructions and all safety...

Page 6: ...tion of these units must comply with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition and other applicable local building codes In Canada the installation of these units must comply with...

Page 7: ...ontal pitch as directed in these instructions and the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 or CSA B149 1 Installation Code Determine that there is not blockage restriction...

Page 8: ...h a diameter 4 inches greater than the vent pipe diameter must be used If there is 6 feet or more of vent pipe prior to passing through the combustible wall or floor then the metal thimble need only b...

Page 9: ...than any part of a building within a horizontal distance of 10 3 05m unless otherwise specified by the American National Fuel Gas Code ANSI Z223 1 or Canada CAN CGA B149 Installation Code The vent mu...

Page 10: ...ombustion which can result in the production of excessive carbon monoxide Follow these guidelines and all applicable codes for all models prior to installing the combustion air duct work WARNING Suffi...

Page 11: ...drip leg should be installed in the vertical pipe run to the unit In some localities codes may require that a manual main shutoff valve and union furnished by installer be installed external to the un...

Page 12: ...putting into service For leak testing on pressures below 20 inches W C Before leak testing close the field installed manual shut off valve shown on Figure 9 on the supply line to isolate the gas valve...

Page 13: ...ssure Input Rating W C kPa BTU Hr W W C kPa BTU Hr W MHU200NG 7 23 1 8 200 000 58 614 6 66 1 66 192 000 56 269 MHU250NG 7 23 1 8 250 000 73 268 6 66 1 66 240 000 70 337 MHU300NG 3 81 0 95 300 000 87 9...

Page 14: ...the side access control compartment of the unit The low voltage thermostat and accessory control devices can be wired to the terminals in the side access control compartment Refer to the wiring diagra...

Page 15: ...Large Unit Heater 15 Operating Instructions and Owner s Manual Main Components FIGURE 10 Line Voltage Thermostat Wiring Connector on Heater S1 S4 M1 VG MC FS S2 S3 S2 CB SE T1 RFC CFC...

Page 16: ...Large Unit Heater 16 Operating Instructions and Owner s Manual Internal Wiring Diagram FIGURE 11...

Page 17: ...field supplied power wires so that they do not come in contact with the flue wrapper or venter housing These hot surfaces may damage the wire s insulation resulting in damage to the unit THERMOSTAT LO...

Page 18: ...puts set it to the maximum rating 7 Observe the pressure rating on the pressure gauge Verify maximum inlet gas supply pressure 8 Turn off all other gas appliances on the same supply line 9 Observe the...

Page 19: ...manifold pressure hose connector using a soap solution or equivalent method as described in ANSI Z223 1 NFPA 54 Prior to Leaving Job Site Prior to leaving the job site verify that Service access door...

Page 20: ...hts burner DO NOT attempt to light the burners manually 5 There is a main shut off valve upstream of the unit Open it See Figure 9 on Page 11 6 Wait five minutes to clear out any gas If you then smell...

Page 21: ...upply Follow lighting instructions to light unit Check burner flame FLUE PASSAGEWAY AND FLUE BOX The flue passages and flue box should be inspected and cleaned prior to each heating season The sequenc...

Page 22: ...old Screws FUEL CONVERSION INSTRUCTIONS FIGURE 15 Rotation of the Valve Manifold Assembly ROTATE valve manifold assembly The heater is standard manufactured for operation with natural gas In case of u...

Page 23: ...NOT FOLLOWED EXACTLY A FIRE EXPLOSION OR PRODUCTION OF CARBON MONOXIDE MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE THE QUALIFIED SERVICE AGENCY PERFORMING THIS WORK ASSUMES RES...

Page 24: ...space tightly sealed building 1 Remove obstruction or correct vent lengths 2 Replace wiring or hose connections 3 Replace pressure switch The control board does not send spark to the electrode 1 The e...

Page 25: ...ontrol board does not send 120 VAC to the air movement fan after approx 30 seconds after ignition and if contact relay fan control is open and there isn t 24VAC on relay fan control 3 The control boar...

Page 26: ...er listed on the unit rating plate Mr Heater Large Unit Heater Model MHU200NG MHU250NG MHU300NG MHU400NG Liquid Propane to Natural Gas Conversion Kit MHU200NG F260165 MHU250NG F260166 MHU300NG F260167...

Page 27: ...60291 60291 60291 60291 20 BLOWER DRIVE RELAY 60292 60292 60292 60292 21 PRESSURE SWITCH 60293 60294 60294 60294 22 DETECTION ELECTRODE 60295 60295 60295 60295 23 MANUAL RESET SAFETY THERMOSTAT 140 C...

Page 28: ...001 Address any Warranty Claims to the Service Department Mr Heater Inc 4560 W 160TH ST CLEVELAND OHIO 44135 Include your name address and telephone number and include de tails concerning the claim Al...

Reviews: