MrHeater MHU200NG Operating Instructions And Owner'S Manual Download Page 8

Large Unit Heater

8

Operating Instructions and Owner’s Manual

• 

Vent must terminate a minimum of 4 feet above grade level 
and must extend beyond any combustible overhang. When 
condensation may be a problem, the vent system shall not 
terminate over public walkways or over an area where condensate 
or vapor could create a nuisance or hazard or could be 
detrimental to the operation of regulators, relief openings, or 
other equipment.

• 

The vent terminal must be installed to prevent any blockage by 
snow and protect building material from degradation by flue 
gases.

• 

The vent cap must be a minimum of 6 inches from the sidewall of 
the building.

• 

Vent must be a minimum of 36 inches below or extend beyond 
any combustible overhang.

• 

Consult NFPA ANSI Z223.1 Gas Vent Termination criteria for vents 
that terminate on a roof pitch that exceeds 9:12.

• 

Canada: vents must terminate a minimum of 3 feet (914mm) from 
a window or door that may be opened, and a non-mechanical air 
supply inlet or combustion air inlet into the building.

TABLE 4

Vent Pipe Diameters and Equivalent Vent Pipe 

Lengths for Horizontal Venting Systems

Model

Vent Pipe 

Diameter

Equivalent Vent Length

Minimum

Maximum

MHU200NG

4”

3’

70’

MHU250NG

6”

3’

70’

MHU300NG

MHU400NG

General Venting Requirements

FIGURE 5

Listed Terminal

“H” Min.

4’ Min.

12” Min. 

Recommended

Tee with drip leg and 

cleanout cap (slope 

1/4” per foot 

downward toward 

drip leg)

Exhaust

Roof Flashing

Use listed 
thimble 
through roof 
and ceiling

When possible, avoid venting through an unconditioned space. 
Venting through an unconditioned space promotes condensation. 
When venting through an unconditioned space is unavoidable, or if 
the unit is installed in an area that is prone to condensation, insulate 
venting runs greater than 5 feet to minimize the production of 
condensation. Inspect for leakage prior to insulating the venting and 
only use insulation that is non-combustible with a temperature rating 
of not less than 500��F. It is recommended that the venting system is 
installed with a tee, drip leg, and clean-out cap as shown in Figure 5.

When venting pipe passes through a combustible interior wall or 
floor, a metal thimble with a diameter 4 inches greater than the vent 
pipe diameter must be used. If there is 6 feet or more of vent pipe 
prior to passing through the combustible wall or floor, then the metal 
thimble need only be 2 inches greater than the vent pipe diameter. 
If a metal thimble is not used, all clearance to combustibles from the 
vent pipe must be 6 inches. Where permitted, type B vent may be 
used for the last section of vent pipe to reduce the required clearance 
to combustibles when passing through a combustible wall or floor. 
When using type B venting, follow the manufacturer’s recommended 
clearance to combustibles. Any material used to close or insulate the 
opening must be non-combustible.

How to attach a single wall vent terminal to double wall (Type B) vent 
pipe:

1. Look for the “flow” arrow on the vent pipe.

2. Slide the vent terminal inside the exhaust end of the double wall 

vent pipe.

3. Drill 3 holes through the pipe and the vent terminal. Using 3/4” 

long sheet metal screws, attach the cap to the pipe. Do not 
overtighten.

How to connect a single wall vent system to a double wall (Type B) 
vent pipe:

1. Slide the single wall pipe inside the inner wall of the double wall 

pipe.

2. Drill 3 holes through both walls of the single and double wall vent 

pipes. Using 3/4” sheet metal screws, attach the 2 pieces of pipe. 
Do not overtighten.

3. The gap between the single and double wall pipe must be sealed 

but it is not necessary to fill the full volume of the annular area. To 
seal, run a large bead of 500��F silastic around the gap.

VERTICAL VENTING

An appliance that operates with a positive vent static pressure 
and with a vent gas temperature that avoids excessive condensate 
production in the vent is said to be ‘Category III’. This unit heater is 
considered a Category III appliance if the venting system meets all of 
the following criteria:

•   The vent system terminates vertically (up).

•  The length of the horizontal portion of the vent run is less than 75% 

of the vertical rise length. (e.g.- If the vertical vent height is 10 feet, 
the horizontal run is less than 7-1/2 feet).

•  Horizontal sections of the vent pipe must be installed with an 

upward slope from the appliance at a pitch of 1/4 inch per foot and 
suspended securely from overhead structures at points not greater 
than 3’ apart.

•  The vent terminates a minimum of 5 feet above the vent connection 

on the unit.

Summary of Contents for MHU200NG

Page 1: ...o this manual For assistance or additional information consult a qualified installer service agency or the gas supplier WHAT TO DO IF YOU SMELL GAS DO NOT try to light appliance DO NOT touch any elect...

Page 2: ...E INSTRUCTIONS BEFORE YOU OPERATE THIS HEATER WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Be sure to read and und...

Page 3: ...perly Set ________________________________ Furnace BTU input _____________________________________ Level ___________________________________________________ Line Pressure _____________________________...

Page 4: ...al Standard Institute Inc 11 West 42nd Street New York NY 10036 These units are CSA International design certified These unit heaters are certified for installation to combustible material as listed i...

Page 5: ...nual is to provide information regarding safety design guidelines installation operation and maintenance of the this gas fired unit heater You must read and understand the instructions and all safety...

Page 6: ...tion of these units must comply with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition and other applicable local building codes In Canada the installation of these units must comply with...

Page 7: ...ontal pitch as directed in these instructions and the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 or CSA B149 1 Installation Code Determine that there is not blockage restriction...

Page 8: ...h a diameter 4 inches greater than the vent pipe diameter must be used If there is 6 feet or more of vent pipe prior to passing through the combustible wall or floor then the metal thimble need only b...

Page 9: ...than any part of a building within a horizontal distance of 10 3 05m unless otherwise specified by the American National Fuel Gas Code ANSI Z223 1 or Canada CAN CGA B149 Installation Code The vent mu...

Page 10: ...ombustion which can result in the production of excessive carbon monoxide Follow these guidelines and all applicable codes for all models prior to installing the combustion air duct work WARNING Suffi...

Page 11: ...drip leg should be installed in the vertical pipe run to the unit In some localities codes may require that a manual main shutoff valve and union furnished by installer be installed external to the un...

Page 12: ...putting into service For leak testing on pressures below 20 inches W C Before leak testing close the field installed manual shut off valve shown on Figure 9 on the supply line to isolate the gas valve...

Page 13: ...ssure Input Rating W C kPa BTU Hr W W C kPa BTU Hr W MHU200NG 7 23 1 8 200 000 58 614 6 66 1 66 192 000 56 269 MHU250NG 7 23 1 8 250 000 73 268 6 66 1 66 240 000 70 337 MHU300NG 3 81 0 95 300 000 87 9...

Page 14: ...the side access control compartment of the unit The low voltage thermostat and accessory control devices can be wired to the terminals in the side access control compartment Refer to the wiring diagra...

Page 15: ...Large Unit Heater 15 Operating Instructions and Owner s Manual Main Components FIGURE 10 Line Voltage Thermostat Wiring Connector on Heater S1 S4 M1 VG MC FS S2 S3 S2 CB SE T1 RFC CFC...

Page 16: ...Large Unit Heater 16 Operating Instructions and Owner s Manual Internal Wiring Diagram FIGURE 11...

Page 17: ...field supplied power wires so that they do not come in contact with the flue wrapper or venter housing These hot surfaces may damage the wire s insulation resulting in damage to the unit THERMOSTAT LO...

Page 18: ...puts set it to the maximum rating 7 Observe the pressure rating on the pressure gauge Verify maximum inlet gas supply pressure 8 Turn off all other gas appliances on the same supply line 9 Observe the...

Page 19: ...manifold pressure hose connector using a soap solution or equivalent method as described in ANSI Z223 1 NFPA 54 Prior to Leaving Job Site Prior to leaving the job site verify that Service access door...

Page 20: ...hts burner DO NOT attempt to light the burners manually 5 There is a main shut off valve upstream of the unit Open it See Figure 9 on Page 11 6 Wait five minutes to clear out any gas If you then smell...

Page 21: ...upply Follow lighting instructions to light unit Check burner flame FLUE PASSAGEWAY AND FLUE BOX The flue passages and flue box should be inspected and cleaned prior to each heating season The sequenc...

Page 22: ...old Screws FUEL CONVERSION INSTRUCTIONS FIGURE 15 Rotation of the Valve Manifold Assembly ROTATE valve manifold assembly The heater is standard manufactured for operation with natural gas In case of u...

Page 23: ...NOT FOLLOWED EXACTLY A FIRE EXPLOSION OR PRODUCTION OF CARBON MONOXIDE MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE THE QUALIFIED SERVICE AGENCY PERFORMING THIS WORK ASSUMES RES...

Page 24: ...space tightly sealed building 1 Remove obstruction or correct vent lengths 2 Replace wiring or hose connections 3 Replace pressure switch The control board does not send spark to the electrode 1 The e...

Page 25: ...ontrol board does not send 120 VAC to the air movement fan after approx 30 seconds after ignition and if contact relay fan control is open and there isn t 24VAC on relay fan control 3 The control boar...

Page 26: ...er listed on the unit rating plate Mr Heater Large Unit Heater Model MHU200NG MHU250NG MHU300NG MHU400NG Liquid Propane to Natural Gas Conversion Kit MHU200NG F260165 MHU250NG F260166 MHU300NG F260167...

Page 27: ...60291 60291 60291 60291 20 BLOWER DRIVE RELAY 60292 60292 60292 60292 21 PRESSURE SWITCH 60293 60294 60294 60294 22 DETECTION ELECTRODE 60295 60295 60295 60295 23 MANUAL RESET SAFETY THERMOSTAT 140 C...

Page 28: ...001 Address any Warranty Claims to the Service Department Mr Heater Inc 4560 W 160TH ST CLEVELAND OHIO 44135 Include your name address and telephone number and include de tails concerning the claim Al...

Reviews: