MrHeater MHU200NG Operating Instructions And Owner'S Manual Download Page 14

Large Unit Heater

14

Operating Instructions and Owner’s Manual

ELECTRICAL REQUIREMENTS

 

WARNING

Shock hazard. Disconnect power supply before 
making wiring connections to prevent electrical 
shock and equipment damage. All appliances 
must be wired strictly in accordance with wiring 
diagram furnished with the appliance. Any wiring 
different from the wiring diagram could result in a 
hazard to persons and property.
Ensure that the supply voltage to the appliance, 
as indicated on the rating plate, is not 5% greater/
less than rated voltage.
Any original factory wiring that requires replace-
ment must be replaced with wiring material hav-
ing a temperature rating of at least 221

º

F (105

º

C).

• 

Installation of wiring must conform with local building codes, 
or in the absence of local codes, with the National Electric Code 
ANSI/NFPA 70 - Latest Edition. Unit must be electrically grounded 
in conformance to this code. In Canada, wiring must comply with 
CSA C22.1, Part 1, Electrical Code.

• 

Two copies of the unit wiring diagram are provided with each 
unit. One is located in the side access control compartment and 
the other is supplied in the literature packet. Refer to this diagram 
for all wiring connections.

• 

Make sure all multi-voltage components (motors, transformers, 
etc.) are wired in accordance with the power supply voltage.

• 

The power supply to the unit must be protected with a fused 
or circuit breaker switch, so that power can be turned off for 
servicing.

TABLE 9: Electrical Specifications

Power Supply

[V]

[A]

[Hz]

[Ph]

[W]

MHU200NG

120

6.3

60

1

756

MHU250NG

120

6.3

60

1

756

MHU300NG

120

10

60

1

1,200

MHU400NG

120

10

60

1

1,200

External electrical service connections that must be installed include:

a. Supply power connection (115, 208, 230, 460, or 575 volts).

b. Connection of thermostats, or any other accessory control devices 
that may be supplied (24 volts).

All supply power electrical connections are made in the side access 
control compartment of the unit. The low voltage (thermostat and 
accessory control devices) can be wired to the terminals in the side 
access control compartment. Refer to the wiring diagram for the 
terminal location of all low voltage wiring.

NOTICE:

 These unit heaters use a direct spark ignition system. There 

is no pilot necessary as the spark lights the main burner as the gas 
valve is turned on. The direct spark ignition control board emits radio 
noise during burner ignition. The level of energy may be enough to 
disturb a logic circuit in a microprocessor controlled thermostat. It is 
recommended that an isolation relay be used when connecting the 
unit heater to a microprocessor controlled thermostat. Select circuit 
protection and wire size according to the unit rating plate. Remove 
electrical junction box cover and connect wiring through knockout 

on the junction box located on the side of the heater. Refer to heater 
wiring diagram for connection information. Use a wire for line power 
connections with proper section size according to the electrical  power 
data indicated in 

Table 9

 and its length. Make sure to connect line 

power to wires located in the external electrical junction box behind 
junction box cover. DO NOT CONNECT LINE POWER TO THERMOSTAT 
TERMINAL STRIP ON OUTSIDE OF HEATER.

Electrically ground the unit in accordance with local codes or in the 
absence of local codes, in accordance with the current National 
Electrical Code (ANSI/NFPA No. 70) in the USA, and in Canada with 
the current Canadian Electrical Code, Part 1 CSA C22.1.

Un-insulated ground wire must be wrapped in electrical tape to avoid 
damage to the electrical system.

• 

Make line voltage connections as shown in Figure 10. Connect 
field wiring as shown on wiring diagram on unit. Also, refer to 
typical diagram in this manual.

• 

To use the blower for air circulation only, your thermostat must 
have a “fan only” or fan selection setting. In case your thermostat 
has this option, an additional wire should be run to the 
 “

”terminal on the thermostat connection block. See wiring 

schematic in Figure 11 .

Summary of Contents for MHU200NG

Page 1: ...o this manual For assistance or additional information consult a qualified installer service agency or the gas supplier WHAT TO DO IF YOU SMELL GAS DO NOT try to light appliance DO NOT touch any elect...

Page 2: ...E INSTRUCTIONS BEFORE YOU OPERATE THIS HEATER WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Be sure to read and und...

Page 3: ...perly Set ________________________________ Furnace BTU input _____________________________________ Level ___________________________________________________ Line Pressure _____________________________...

Page 4: ...al Standard Institute Inc 11 West 42nd Street New York NY 10036 These units are CSA International design certified These unit heaters are certified for installation to combustible material as listed i...

Page 5: ...nual is to provide information regarding safety design guidelines installation operation and maintenance of the this gas fired unit heater You must read and understand the instructions and all safety...

Page 6: ...tion of these units must comply with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition and other applicable local building codes In Canada the installation of these units must comply with...

Page 7: ...ontal pitch as directed in these instructions and the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 or CSA B149 1 Installation Code Determine that there is not blockage restriction...

Page 8: ...h a diameter 4 inches greater than the vent pipe diameter must be used If there is 6 feet or more of vent pipe prior to passing through the combustible wall or floor then the metal thimble need only b...

Page 9: ...than any part of a building within a horizontal distance of 10 3 05m unless otherwise specified by the American National Fuel Gas Code ANSI Z223 1 or Canada CAN CGA B149 Installation Code The vent mu...

Page 10: ...ombustion which can result in the production of excessive carbon monoxide Follow these guidelines and all applicable codes for all models prior to installing the combustion air duct work WARNING Suffi...

Page 11: ...drip leg should be installed in the vertical pipe run to the unit In some localities codes may require that a manual main shutoff valve and union furnished by installer be installed external to the un...

Page 12: ...putting into service For leak testing on pressures below 20 inches W C Before leak testing close the field installed manual shut off valve shown on Figure 9 on the supply line to isolate the gas valve...

Page 13: ...ssure Input Rating W C kPa BTU Hr W W C kPa BTU Hr W MHU200NG 7 23 1 8 200 000 58 614 6 66 1 66 192 000 56 269 MHU250NG 7 23 1 8 250 000 73 268 6 66 1 66 240 000 70 337 MHU300NG 3 81 0 95 300 000 87 9...

Page 14: ...the side access control compartment of the unit The low voltage thermostat and accessory control devices can be wired to the terminals in the side access control compartment Refer to the wiring diagra...

Page 15: ...Large Unit Heater 15 Operating Instructions and Owner s Manual Main Components FIGURE 10 Line Voltage Thermostat Wiring Connector on Heater S1 S4 M1 VG MC FS S2 S3 S2 CB SE T1 RFC CFC...

Page 16: ...Large Unit Heater 16 Operating Instructions and Owner s Manual Internal Wiring Diagram FIGURE 11...

Page 17: ...field supplied power wires so that they do not come in contact with the flue wrapper or venter housing These hot surfaces may damage the wire s insulation resulting in damage to the unit THERMOSTAT LO...

Page 18: ...puts set it to the maximum rating 7 Observe the pressure rating on the pressure gauge Verify maximum inlet gas supply pressure 8 Turn off all other gas appliances on the same supply line 9 Observe the...

Page 19: ...manifold pressure hose connector using a soap solution or equivalent method as described in ANSI Z223 1 NFPA 54 Prior to Leaving Job Site Prior to leaving the job site verify that Service access door...

Page 20: ...hts burner DO NOT attempt to light the burners manually 5 There is a main shut off valve upstream of the unit Open it See Figure 9 on Page 11 6 Wait five minutes to clear out any gas If you then smell...

Page 21: ...upply Follow lighting instructions to light unit Check burner flame FLUE PASSAGEWAY AND FLUE BOX The flue passages and flue box should be inspected and cleaned prior to each heating season The sequenc...

Page 22: ...old Screws FUEL CONVERSION INSTRUCTIONS FIGURE 15 Rotation of the Valve Manifold Assembly ROTATE valve manifold assembly The heater is standard manufactured for operation with natural gas In case of u...

Page 23: ...NOT FOLLOWED EXACTLY A FIRE EXPLOSION OR PRODUCTION OF CARBON MONOXIDE MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE THE QUALIFIED SERVICE AGENCY PERFORMING THIS WORK ASSUMES RES...

Page 24: ...space tightly sealed building 1 Remove obstruction or correct vent lengths 2 Replace wiring or hose connections 3 Replace pressure switch The control board does not send spark to the electrode 1 The e...

Page 25: ...ontrol board does not send 120 VAC to the air movement fan after approx 30 seconds after ignition and if contact relay fan control is open and there isn t 24VAC on relay fan control 3 The control boar...

Page 26: ...er listed on the unit rating plate Mr Heater Large Unit Heater Model MHU200NG MHU250NG MHU300NG MHU400NG Liquid Propane to Natural Gas Conversion Kit MHU200NG F260165 MHU250NG F260166 MHU300NG F260167...

Page 27: ...60291 60291 60291 60291 20 BLOWER DRIVE RELAY 60292 60292 60292 60292 21 PRESSURE SWITCH 60293 60294 60294 60294 22 DETECTION ELECTRODE 60295 60295 60295 60295 23 MANUAL RESET SAFETY THERMOSTAT 140 C...

Page 28: ...001 Address any Warranty Claims to the Service Department Mr Heater Inc 4560 W 160TH ST CLEVELAND OHIO 44135 Include your name address and telephone number and include de tails concerning the claim Al...

Reviews: