T: +1-613-545-0466 F: +1-613-542-8029 www.mrel.com
33
center conductor and the shielding connections do not touch each other. It
is a good idea to check the total resistance of the
PROBECABLE
and coaxial
cable circuit at the BNC connector using a blaster’s galvanometer to ensure
that there are no bad connections.
10. At the
DataTrap II™
Data/VOD Recorder
end, connect the coaxial cables to
the input connectors (labeled
1 2 3 4 5 6 7 8
) located on the outside and at
the back of the
DataTrap II™
Data/VOD Recorder
.
11. The
PROBECABLE
installation aspects of the test are complete. The
DataTrap II™
Data/VOD Recorder
is now ready to be prepared to record the
test.
5.4.2 Preparation Of Probecable For Multiple Blasthole Recording
1. Prepare the end of the
PROBECABLE
by using the wire cutters to remove
the insulation from the end. Then short the
PROBECABLE
by connecting
the shielding wire to the center conductor wire and twist them together.
Protect the connection well with electrical tape.
2. Start with the blasthole that is designed to detonate first of the multiple
holes to be recorded by the
DataTrap II™
Data/VOD Recorder
.
Using tape or wire, attach the short circuit end of the
PROBECABLE
to the booster or to a rock, and lower the
PROBECABLE
into the hole.
Detonation cord downlines may damage the
PROBECABLE
or cause side
initiation of the bulk explosive. When initiating with detonation cord,
attach the
PROBECABLE
to a rock and lower it on the side of the hole
opposite to the detonation cord downline.
3. Run the
PROBECABLE
between the first hole and the second hole leaving
sufficient slack between the holes to allow for ground movement between
the delayed holes. Excess
PROBECABLE
between holes is not a concern
for the
DataTrap II™
Data/VOD Recorder
.
4. Each blasthole following the first hole will require a doubled length of
PROBECABLE
in order to form a continuous circuit throughout
the blast. There are two common methods of lowering a doubled length of
PROBECABLE
in these holes. The first and simplest method
is to run the
PROBECABLE
through a wire loop that has been tied or taped around a rock or booster. This allows the rock to slide
along the
PROBECABLE
as the
PROBECABLE
is lowered into the hole, until the rock reaches the bottom of the hole. The second method
is to measure out the midpoint of the length of
PROBECABLE
that is to be lowered into the hole, and attach the rock or booster so that
it reaches the exactly the bottom of the hole when inserted.
5. After the last hole to be recorded has been loaded with
PROBECABLE
, the
PROBECABLE
can then be cut at the top of that hole.
6. Note the Unit Resistance of the probe by reading the value in ohm/m or ohm/ft from the
MREL
factory label on the spool of
PROBECABLE
. Note the ohm/m value if the
VOD
is to be reported in m/s. Note the ohm/ft value if the
VOD
is to be reported in
ft/sec. The
Unit Resistance
information will be requested later by the
DAS™ Data Acquisition Suite
. When measured with a Blaster’s
galvanometer, the Probe Resistance should compare favorably with the calculated resistance of the
PROBECABLE
(Unit Resistance
multiplied by its length). If this is not the case then remove the length of
PROBECABLE
and reload another length into the hole.
7. The hole can now be loaded with explosives and stemming per usual procedure. Hold the
PROBECABLE
taut during the loading of
the explosive to avoid slack in the hole. If you will not be present during loading, tie the
PROBECABLE
taut around a hole marker
stake, or around a rock at the top of the borehole. After loading, you may wish to check the Probe Resistance with a digital
Blaster’s
Galvanometer
to ensure that no damage has occurred to the
PROBECABLE
.
8. Do not use a standard mulitmeter because they can put too much current through the cable.
9. At the top of the last hole, connect the
PROBECABLE
to the coaxial cable using the wire cutters and electrical tape. The connection
Figure 3
Summary of Contents for DATA TRAP II
Page 5: ...T 1 613 545 0466 F 1 613 542 8029 www mrel com 1 Chapter 1 Getting Started...
Page 7: ...T 1 613 545 0466 F 1 613 542 8029 www mrel com 3 Chapter 2 Introduction...
Page 11: ...T 1 613 545 0466 F 1 613 542 8029 www mrel com 7 Chapter 3 Hardware...
Page 25: ...T 1 613 545 0466 F 1 613 542 8029 www mrel com 21 Chapter 4 Memory And Triggering...
Page 28: ...DataTrap II Operations Manual Edition 5 4 24...
Page 29: ...T 1 613 545 0466 F 1 613 542 8029 www mrel com 25...
Page 30: ...DataTrap II Operations Manual Edition 5 4 26...
Page 50: ...DataTrap II Operations Manual Edition 5 4 46...
Page 51: ...T 1 613 545 0466 F 1 613 542 8029 www mrel com 47 Chapter 7 Strain Gauge Upgrade...
Page 59: ...T 1 613 545 0466 F 1 613 542 8029 www mrel com 55...