5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
65
4349322/01 EN
VACUTAP
®
VV
®
5.3.5.1.4 Securing on-load tap-changer head cover
NOTICE
Damage to the on-load tap-changer!
A missing or damaged o-ring as well as unclean sealing surfaces lead to in-
sulating fluid escaping and therefore to damage to the on-load tap-changer.
► Ensure that the o-ring is positioned untwisted in the on-load tap-changer
head cover.
► Ensure that the o-ring does not become damaged when mounting the
cover.
► Ensure that the sealing surfaces on the on-load tap-changer head cover
and on-load tap-changer head are clean.
► Place on-load tap-changer head cover on on-load tap-changer head and
secure.
Figure 46: On-load tap-changer head cover
5.3.5.2 Vapor-phase drying in the autoclave
If you wish to perform another transformer ratio test after drying, proceed as
described in the section "Performing transformer ratio test following dry-
ing" [