5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
95
4983703/01 EN
VACUTAP
®
VV-Ex
The inner tube must not be deformed and must be deburred in order to slide
easily in the outer tube.
Figure 82: Deburring the inner tube
Dimension A (= distance between
the shaft end of the drive and the
shaft end of bevel gear)
Inner tube
Outer tube
170 mm...190 mm
Shorten to 200 mm
= 200 mm
191 mm...1130 mm
Dimension A + 20 mm
= 200 mm
1131 mm...1598 mm
= 700 mm
= 1150 mm
1,599 mm...2,009 mm
= 1150 mm
= 1,150 mm