5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
84
4983703/01 EN
VACUTAP
®
VV-Ex
10. Install a stop-cock with a nominal width of at least 25 mm between the
protective relay and oil conservator.
Figure 65: Stop-cock
5.5.2.4 Installing electrics for protective relay
The protective relay's dry-reed magnetic switch is supplied as either an NC
or NO contact in the following variants:
▪ 2 x NC contact
▪ 2 x NO contact
▪ 1 x NC contact and 1x NO contact
WARNING
Risk of death or severe injury!
Risk of death or severe injury due to improper electrical connection of the
protective relay.
► Loop the protective relay into the tripping circuit of the circuit breakers of
the transformer to be protected so that the transformer is immediately de-
energized by the circuit breakers when the protective relay is tripped.
► Systems which only generate an alarm message are not permitted.