5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
110
4983703/01 EN
VACUTAP
®
VV-Ex
10. Use the grounding cable and the supplied screw with the contact wash-
ers to establish a connection between the protective cover and the func-
tional ground. Due to the risk of collision with the screw head, fit the fix-
ing screw for the grounding cable from the inside.
Figure 102: Screwing down the grounding cable of the protective cover
5.5.4.2.1 On-load tap-changer sets and combinations
For two-column and three-column on-load tap-changer models, the individ-
ual on-load tap-changer columns are driven by a common motor-drive unit.
You must couple the on-load tap-changer heads above the transformer
cover together and ensure synchronous switching of the on-load tap-
changer columns.
Proceed as follows:
1. Check that the operating positions of all on-load tap-changers are identi-
cal (inspection window in the on-load tap-changer head). Each on-load
tap-changer must be in the adjustment position.
2. Turn the pressure segments of upper gear units to one side by loosening
the 6 M8 bolts / wrench size 13.