5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
89
4983703/01 EN
VACUTAP
®
VV-Ex
Figure 73: Permitted maximum axial displacement of horizontal drive shaft
Resistance to corrosion of components
Square tubes, coupling brackets, coupling bolts, screws, and locking wash-
ers are corrosion-resistant. We therefore recommend not applying the same
external coating to these parts as to the transformer tank.
Cutting square tubes, telescopic protective tubes, and protective cover
The square tubes, telescopic protective tubes, and protective cover are sup-
plied in overlengths (graded standard lengths). You must cut these parts to
the required size before mounting on the transformer. In rare cases, you also
have to cut the inner tube of the telescopic protective tube to the desired
length. The maximum total drive shaft length of the drive - last column = 15
m.
Standard lengths
Ex TAPMOTION® ED
400
•
600
•
900
•
1,300
•
1,700
•
Table 13: Graded standard lengths of square tubes for explosion-proof motor-drive unit
TAPMOTION® ED-Ex