5 Installation and commissioning
71
BA5831400-00 EN
ü
Open the cover plate.
1. Determine the necessary resistance value from the setting curve (8.6 Ω in
this example).
2. Remove the bridge at terminals
and
.
Figure 54: Bridge
3. Connect an ohmmeter to terminals
and
.
4. Set the required resistance value using the adjusting screw of the poten-
tiometer. Turning the adjusting screw to the right causes the resistance
value to increase, and turning it to the left causes it to decrease.
Figure 55: Potentiometer adjusting screw
Summary of Contents for MESSKO MT-ST Compact
Page 25: ...3 Product description 25 BA5831400 00 EN 3 6 Nameplate Figure 9 Nameplate ...
Page 78: ...8 Disposal 78 BA5831400 00 EN Observe the national disposal regulations in the country of use ...
Page 90: ...10 Appendix 90 BA5831400 00 EN NPT adapters optional Figure 73 NPT adapters 1 2 NPT 3 4 NPT ...