5 Installation and commissioning
30
BA5831400-00 EN
NOTICE
Damage to the device!
If you kink the capillary line or carry the device by the capillary line, the de-
vice can become damaged and display incorrect measured values as a re-
sult.
► Carefully remove the device from the packaging.
► Never carry the device by the capillary line.
► Do not damage the capillary line and sensor.
► Unroll the capillary line without bending or kinking it.
► Observe the minimum bending radius of 50 mm.
5.1 Transporting in the installed state
If transportation of the entire assembled unit is necessary between mounting
the device onto the transformer / oil conservator and commissioning it,
please also refer to the information on further transport [
28].
NOTICE
Damage to the device
The device can become damaged during transport due to unsuitable pack-
aging.
► Use suitable packaging for transporting the device in the installed state.
► Protect the device against mechanical damage.
► Prevent the ingress of rain water.
► Ensure sufficient air ventilation without the formation of condensation.
5.2 Checking measured temperature values
Before attaching the pointer thermometer, you can check the accuracy of the
display with a reference measurement. The pointer thermometer is cali-
brated at the factory.
ü
Only perform a reference measurement in moving liquid baths. Use of the
MZT1650S calibration bath offered by Messko is recommended.
ü
The temperature of the liquid bath must remain constant for 15 minutes.
ü
Use an additional, calibrated glass thermometer to perform the reference
measurement.