Alarms ‘RC’
RC unit uses one alarm output to interface with R Series. If a fault occurs, a signal is sent
to the alarm circuit on R Series, which, typically, will put machine tool into a feed hold. The
units PLC will display fault type.
Alarm will not clear off PLC display until fault has been rectified. Once fault has been
remedied, press
[ 1 ]
to clear alarm.
ALARM DISPLAY
SYMPTOM(S)
CAUSE
LOW FLOW
Less than 5GPM through heat
exchanger
Heat exchanger
clogged.
Circulation pump
rotation reversed.
OVERLOAD
Motor overload tripped
Electric motor short
cycle.
Electric motor shorting.
Load on motor to great.
Electric motor over load
set to low.
Electrical short in system
causing overload to trip.
INLET OUT OF RANGE
Sensor fault
Inlet temperature out of
range.
OUTLET OUT OF RANGE
Sensor fault
Outlet temperature out
of range.
HP PUMP FAULT
R Series high pressure system
fault
R Series Fault.
Summary of Contents for AK CB20
Page 15: ...9 MPSYSTEMS M 001 06 4 2 1 Floor Layout R VR SERIES 28 36 15 24 ...
Page 16: ...10 MPSYSTEMS M 001 06 RF16 RT VR16 VRT SERIES 15 24 38 42 ...
Page 25: ...19 MPSYSTEMS M 001 06 6 3 3 1 R RA11 Series Control Signal Explanation ...
Page 26: ...20 MPSYSTEMS M 001 06 6 3 3 1 1 Variable Adaptive Series Control Signal Explanation VR ...
Page 33: ...27 MPSYSTEMS M 001 06 6 5 3 8JIC to 6JIS Fitting Explanation ...
Page 72: ...66 MPSYSTEMS M 001 06 10 2 Relief Valve Identifier ...
Page 76: ...70 MPSYSTEMS M 001 06 JIS JIC Fittings Example 6 3 8 JIS 6 3 8 JIC 8 1 2 JIS 8 1 2 JIC ...
Page 77: ...71 MPSYSTEMS M 001 06 RF8 Series Flow Diagram ...
Page 78: ...72 MPSYSTEMS M 001 06 RFC Series Flow Diagram ...
Page 79: ...73 MPSYSTEMS M 001 06 RA11 Series Flow Diagram ...
Page 80: ...74 MPSYSTEMS M 001 06 RT Series Flow Diagram ...
Page 81: ...75 MPSYSTEMS M 001 06 RF16 Series Flow Diagram ...