GSM-204-423
Connecting 230 V 3-phase (delta) ac power cables
31st Oct 01
Installation & Configuration: Horizon
macro outdoor
68P02902W03-A
CONTROLLED INTRODUCTION
Inst. 3–29
Connecting
230 V ac
3-phase (delta)
mains input
cables
To connect the earth, 3-phase (delta) cables to the number 1 ac distribution box:
1.
Connect the mains input earth cable (green/yellow) to terminal 1 of the
earth terminal block in the number 1 ac distribution box, and check the
connection of the main chassis earth cable to terminal 2. Secure both
cables.
2.
Secure the screen at the cabinet entry gland.
3.
Connect the phase 1 cable (red), to terminal D2 of the four pole MCB in
the number 1 ac distribution box, and secure.
4.
Connect the phase 2 cable (yellow), to terminal C2 of the four pole MCB in
the number 1 ac distribution box, and secure.
5.
Connect the phase 3 cable (blue), to terminal B2 of the four pole MCB in
the number 1 ac distribution box, and secure.
6.
Refit the previously retained cover of the number 1 ac distribution box.