SCHEMES FOR TESTS
04.
COMPONENTS TEST
To detect if the failure is in the control board or in the motor, it is necessary to perform tests
with a direct connection to a 230V power supply. In the diagrams below, it is shown how this
connection should be made and how to interleave the different components wires.
Make the connections as shown in the
picture.
If the motor runs, the problem is in the
control board. Changing the wires in
the battery, changes the direction of
movement of the motor.
The test must be carried out by specialized technicians due to the serious danger
related to the misuse of electrical systems !!
To perform the tests, you do not need to remove the automation from where it is installed.
This way you can see if the automation directly connected to the current can work properly.
The chain must be installed
with an interleaved plastic
fuse link, with maximum
tensile strength of
70Kg
04.
COMPONENTS TEST
CHAIN RESISTANCE AND WEIGHT
The maximum weight allowed
for the chain is
20Kg