6. Operation
46
Indicator light
name
Active indi
-
cator light
Inactive indi
-
cator light
Alarm
Exit activated
This alarm is activated when the control unit sends information that the red light of the control unit is acti-
vated.
The ALARM output is not activated, after the light is turned off, the alarm disappears automatically.
This output is active when the control unit sends an active "red light" flag, that is, it has detected a critical
malfunction. Do not run the engine until a service check is carried out.
This flag is taken from DM1 on J1939 standard ECUs. Some controllers provide this flag in their own pro
-
prietary frames, others do not provide the flag.
Engine start waiting
light
D5260640
D5260610
AHI ECU Standby
ECU STANDBY
This alarm is activated when the control unit sends information that the Wait to Start is activated.
The ALARM output is not activated, after the light is turned off, the alarm disappears automatically.
This output is active when the ECU's Wait To Start light is active.
ATT filter indicator
light
D5260320
D5260540
AHI ATT filter indicator
light
ATT FILTER INDICATOR
LIGHT
This alarm is activated when the control unit sends information that the ATT filter indicator light of the con
-
trol unit is activated.
The ALARM output is not activated, after the light is turned off, the alarm disappears automatically.
This output is active when the ATT filter indicator light is active.
Exhaust system
high temperature
indicator light
D5260470
D5260550
AHI ATT HEST indicator
light
ATT HEST INDICATOR
LIGHT
This alarm is activated when the control unit sends information that the ATT Hest indicator light of the con-
trol unit is activated.
The ALARM output is not activated, after the light is turned off, the alarm disappears automatically.
This output is closed if the control unit sends the HEST indicator light signal.
If the ECU stops sending the HEST warning signal, the binary input will be open, regardless of whether the
alarms in the alarm list are acknowledged or not.
SCR error indicator
light
D5260560
D5260570
AHI ATT Error indicator
light
SCR
ATT ERROR INDICATOR
LIGHT
SCR
This alarm is activated when the control unit sends information that the ECU ATT SCR Error indicator light
is activated.
The ALARM output is not activated, after the light is turned off, the alarm disappears automatically.
This output is active when the ATT SCR error indicator light is active.
Regeneration inhib-
it indicator light
D5260460
D5260600
AHI ATT Inhibit indicator
light
ATT INHIBIT INDICATOR
LIGHT
This alarm is activated when the control unit sends information that the ECU ATT inhibit indicator light is
activated.
The ALARM output is not activated, after the light is turned off, the alarm disappears automatically.
This output is active when the ATT inhibit indicator light is active.
Summary of Contents for RENTAL GE 50 KR-5
Page 2: ......
Page 58: ...7 Maintenance 54 NOTES...
Page 66: ...8 Alarms 62 NOTES...
Page 67: ......