39
6. Operation
6.4 Stopping the generating set
1 -
Turn off the loads connected to the generating set.
2 - Set the main machine switch (2) to OFF (insertion lever
downwards).
1
D5260430
3 - Press the stop button (5) to launch the generating set
stop sequence.
The engine stops at the end of the cooling cycle.
For immediate stop, press the stop button (5) again.
Note:
The stop button only works in MAN mode.
5
D5260670
4 - Turn the control panel power switch (2) OFF.
5 -
Wait 2 minutes and turn the battery disconnect switch to
off.
Note:
•
It is important to wait for the indicated time to allow
the engine control unit to record and store the engine
operation data.
2
D5260440
6.5 Emergency stop
For an emergency stop, press the emergency button (6).
To reset the button, turn it clockwise.
6
D5260680
Summary of Contents for RENTAL GE 50 KR-5
Page 2: ......
Page 58: ...7 Maintenance 54 NOTES...
Page 66: ...8 Alarms 62 NOTES...
Page 67: ......