45
6. Operation
6.8 After-treatment status display
The generator control panel provides information on the after-treatment system installed on the generator
engine through the following functions:
•
Universal lamps display (icons).
•
Display of analogue and binary values.
•
Control of the post-treatment regeneration function by transmitting commands to the control unit.
After-treatment screen
The after-treatment screen is automatically displayed once one of the warning lights activates or changes
state.
Disabling the lights will not trigger the screen display.
The screen is then displayed until the operator switches to another screen.
The alarm list screen has a lower priority, so even if a new alarm appears, the post-treatment screen is still
displayed.
To avoid the display of an empty screen, the inactive warning lights are represented by "dotted" icons. If no
warning lights are active, the screen shows all the dashed icons.
Aftertreatment
Aftertreatment
D5260530
Universal lamps (icons)
The icons of the universal lights are shown in the after-treatment screen.
Depending on the value read in a structure with a specific SPN, each lamp icon is:
shown – hidden - slow blinking (1 Hz) - fast blinking (2 Hz)
Note:
•
The flashing light icon is defined as the display of the active light icon and the inverse colour active light
icon at the required frequency.
Indicator light
name
Active indi
-
cator light
Inactive indi
-
cator light
Alarm
Exit activated
Yellow indicator
light
D5260650
D5260630
AHI ECU Yellow indicator
light
ECU YELLOW INDICA
-
TOR LIGHT
This alarm is activated when the control unit sends information that the yellow light of the control unit is
activated.
The ALARM output is not activated, after the light is turned off, the alarm disappears automatically.
Red stop indicator
lamp
D5260480
D5260620
AHI ECU Red indicator
light
ECU RED INDICATOR
LIGHT