ZX Fire Alarm Control Panels
MORLEY-IAS
Installation Manual
Document No. 996-174-000-1, Revision: 01
Page 35
The ZX5Se Fire Alarm Control Panel supervises and charges the two 12-volt batteries that make
up the standby power source. Batteries are available commercially and should be of the sealed,
lead-acid type. Suggested suppliers for the Batteries are Yuasa and Power-Sonic.
Use the current rating chart, along with the following formulae, to determine the size of the
batteries to satisfy the specific installation conditions.
Batteries with capacity greater than 24Ah should be installed in a separate enclosure that is
suitable for Fire Protection Use such as Battery Box – 797-078, with wiring connected to the
panel through conduit.
4.1 Sensor Current Calculations
4.1.1 Quiescent
Load
Refer to the manufacturers’ published data sheets for the supply current required by each sensor
type in normal mode. Take into account the figures quoted for whether the detector LED flashes
when the signalling device is addressed – refer to the Commissioning manual for details of the
Setup parameter to turn this blinking on / off.
Calculate the total current required by the sensors connected to all signalling loops. This should
be based on the quantity of each device installed and the supply current required for the device.
4.1.2 Alarm
Load
Refer to the manufacturer’s published data sheets for the supply current required by each sensor
type.
Calculate the total current required by the sensors connected to all signalling loops. This should
be based on the quantity of each device installed and the supply current required for the device
as above.
When a fire alarm condition is registered, the panel will turn on the sensor LED indicators for the
first four sensors that register an alarm. Refer to the manufacturers’ data sheet for the current
supply required for these LED indicators.
Calculate the total current required by any loop-driven sounders or output modules active in alarm
conditions. NOTE: The LED of all activated System Sensor output modules will be turned ON.
4.1.3 Adjustment
Factors
The figures calculated for sensor current, above, should be multiplied by an adjustment factor of
1.8 before being used in the Current Rating Chart.
4.2 Local Systems Ampere Hour Calculation
Use the following formula to calculate the size
of batteries required for the installation.
C = Total A * 24 hours
D = Total B * 0.5 hours
These installations require a standby period of
24 hours plus thirty minutes of alarm operation
at the end of the standby period.
Battery Ah = 1.25 * (C + D)
Summary of Contents for FW9003 Range
Page 55: ......