ZX Fire Alarm Control Panels
Page 2
Document No. 996-174-000-1, Revision: 01
Installation Manual
CAUTION: A Lithium Battery is used for Data Retention.
Replace only with the same or equivalent type. Contact the Service Organisation for
Replacement CPU Card.
EN54
!
EN54-2 13.7
Maximum of 512
sensors / manual
call points per
panel.
The ZX1Se, ZX2Se and ZX5Se range of panels has many features,
which if used inappropriately, may contravene the requirements of
EN54. Where such a possibility may arise, a suitable warning is given
with brief details of the EN54 requirement and the relevant section it
pertains to. A typical EN54 non-compliance warning is illustrated.
The ZX10Se fire control panel, which comprises two networked ZX5Se
panels within a single enclosure, has a maximum limit of 1024 sensors
/call points.
1.3 National
Approvals
This equipment must be installed in accordance with these instructions and the appropriate
national, regional and local fire systems installation regulations specific to the country and
location of the installation. Consult with the appropriate Authority Having Jurisdiction (AHJ) for
confirmation of the requirements.
All equipment is to be installed in accordance with the appropriate standards for the
country and area of installation.
This equipment must be installed in accordance with these instructions and the appropriate
national, regional and local wiring regulations. In the UK the wiring must conform to the
requirements of the latest edition of the IEE Wiring Regulations.
1.4 EN54
Information
EN54
9
This Fire Control Panel complies with the requirements of EN54-2/4 1997. In addition
to the basic requirements of EN54, the panel conforms to the following optional
functions.
Option EN54-2
Clause
Indication:
Fault signals from points
8.3
Controls: Coincidence
Detection
7.12
Delays of Actioning Outputs
7.11
Disablement of each address point.
9.5
Test
condition
10
Outputs:
Outputs to fire alarm devices
7.8
EN54
9
The power supplies for the ZX1Se, ZX2Se, ZX5Se and ZX10Se range of panels
complies with the following clauses of EN54-4.