ZX Fire Alarm Control Panels
MORLEY-IAS
Installation Manual
Document No. 996-174-000-1, Revision: 01
Page 39
Specification Item
Values
Enclosure
500mm wide, 500mm high, 183 mm deep.
Sealed to IP30.
Weight
19 kg without batteries.
38.8 kg with 24Ah batteries fitted.
Operating Temperature
0 C to +40 C
Relative Humidity
85% (non-condensing)
Knockouts (20mm)
24 (Top), 24 (Bottom)
Sounder Output
4 programmable outputs.
Open- and short-circuit monitored.
6k8, EOL resistors (P/N 170-073-682).
1A maximum output current.
Minimum switched current – 1mA.
Auxiliary Relay
2 volt-free, changeover outputs. Relay 1 configured as Fault
output. Relay 2 configured as Fire output.
Contacts rated at 30V AC/DC, 1 Amp maximum.
Minimum switched load – 1mA @ 5V
Sensor Circuit
1 to 5 plug-in loop driver modules per panel.
Supports Analogue Addressable devices over a 2-wire,
combined-power and digital-data, transmission loop.
Loop Output Voltage and Signalling depends on the loop
driver installed – refer to documentation supplied with the
loop driver.
Maximum Loop Loading is 460mA per loop.
Monitoring zones
Up to 20 zones with individual LED indicators, expandable to
40 / 80 zones with optional LED indicator boards.
Maximum 120 zones – up to 200 software zones
(no LED
indicators).
Table 10 – ZX5Se Functional Specifications