DESCRIPTION

The LT FL20 Series is part of the Fire Alarm Aspiration Sensing 

Technology

®

 (FAAST) family.  FAAST is an advanced fire detection 

system for use where early warning and very early warning are a 

requirement. The system continuously draws air from the controlled 

environment through a series of sampling holes to monitor the 

environment for smoke particulate.
The FL20 is the addressable version of the FAAST LT range, 

communicating with the CIE (Fire Panel) via a proprietary loop 

protocol.  It is available in 3 different models:

FL2011EI -

  Has single channel capability with one laser smoke 

sensor.

FL2012EI -

  Has single channel capability with two laser smoke 

sensors in a common chamber for coincidence 

detection.

FL2022EI -

 Has two channel capability with two laser smoke 

sensors in separate chambers. (one sensor for each 

channel).

This guide provides information for mounting and basic installation 

using the unit’s default factory settings.  For more advanced 

information please see the FAAST LT Advanced Setup and Control 

Guide - reference D200-100-00.

SPECIFICATIONS
Electrical Characteristics

Voltage Range: 

18.5 - 31.5 VDC

Supply Current: 

1 Channel: 

170mA (typical); 360mA (max) @ 

24 VDC 25

o

C (excluding sounders)

 

2 Channel: 

270mA (typical); 570mA (max) @ 

24 VDC 25

o

C (excluding sounders)

Communication Loop Supply Voltage:   15 – 29 VDC (Loop current ≤ 

900mA)

Communication Loop Standby Current:  @ 24V: 900 µA max. (poll once 

every 5s)

Module Isolator Characteristics

Maximum rated switching current  

(under short circuit, Is max): 

0.9A @ ≤  29V

Maximum leakage current (IL max) 

 

with the switch open (isolated state):  15mA

Maximum series impedance with 

the switch closed (Zc max): 

190 m ohm at 15Vdc; 1A

Power Reset: 

0.5s

Configurable Input: Activation Time: 

2s (min)

Relay Contact Ratings: 

2.0 A @ 30 VDC, 0.5A @ 30 VAC

Environmental Ratings

Temperature: 

-10°C to 55°C

Relative Humidity: 

10% to 93% (non-condensing)

IP Rating: 

65

Mechanical

Exterior Dimensions: 

See Figure 1

Wiring: 

0.5 mm² to 2 mm² max

Maximum Single Pipe Length:  

100m (Classes A. B & C) 

Maximum Number of Holes:  

See table 1A

Pipe Spec (EN54-20 Compliance):  

to EN 61386 

 

(Crush 1, Impact 1, Temp 31)

Outside Pipe Diameter: 

25mm (nom) or 27mm (nom)

Shipping Weight: 

6.5kg (inc sensors)

FIRE ALARM ASPIRATION SENSING TECHNOLOGY

®

QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT

MODELS FL2011EI,  FL2012EI  AND FL2022EI

Figure 1: Dimensions and Knock-Outs

E N G L I S H

PARTS LIST
Description Quantity

FAAST LT unit 

1

Mounting bracket 

1

3-pin Terminal block  

6

4-pin Terminal block  

1

2-pin Terminal block  

3

47 k-ohm EOL Resistor  

2

USB Cable 

1

Front Panel Labelling Pack 

1

Installation Kit CD 

1

Quick Installation Guide 

1

Important Note

Aspirating Smoke Detectors supplied and installed within the 

EU must conform to the EU Construction Products Directive 

(89/106/EEC) and the related European Product Standard EN 

54-20. FAAST LT has been tested and certified to ensure that it 

conforms to the necessary Standards, but strict adherence to this 

instruction guide is advised to ensure that the installation meets 

the requirements of the CPD Directive.

367

mm

135 mm

56 mm

44 mm

403

mm

356 mm

Summary of Contents for FL2011EI

Page 1: ...ator Characteristics Maximum rated switching current under short circuit Is max 0 9A 29V Maximum leakage current IL max with the switch open isolated state 15mA Maximum series impedance with the switc...

Page 2: ...xed in place This allows the installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed 1 2 3 4 5 6 7 8 9 10 F...

Page 3: ...Each unit has 2 pipe holes per channel so if installing a 1 channel unit holes 3 and 4 do not function Use Table 1 to locate the holes required for the installation Figure 8 Pipe Holes Table 1 Pipe H...

Page 4: ...EL 2 FILTER POWER AND ALARM CONNECTIONS CHANNEL 1 FILTER USB PORT SENSOR COVER POSITION FOR TEST MAGNET POSITION FOR TEST MAGNET Exhaust Pipe SAMPLING AREA SAMPLING AREA 5 6 EARTH BAR MOUNT EARTH BAR...

Page 5: ...B connection section later in this guide for more information on this and the FAAST LT Advanced Setup and Control Guide EXTERNAL RESET The default setting for the configurable external input is Device...

Page 6: ...Advanced Protocol Flow Level Test Reset and Disable Buttons 11c FL2022EI 2 Channel Detector ALARM PREALARM MODULE LEVEL SMOKE FAULT FAULT POWER IN P U T S E N S O R AS PIR AT OR E L B A S I D M E T S...

Page 7: ...when initialising POWER FAULT ON Yellow Low power alert high power fault Check the power supply voltage CHANNEL FLOW INDICATORS 1 2 ON Green The LED indicates the air flow for a channel Centre normal...

Page 8: ...operation will cause the unit to enter Service Mode The FILTER LEDs will blink the unit will switch off power to the fans and stops communicating with the fire panel the smoke sensors continue to comm...

Page 9: ...generateconfigurationparameters for correct set up and operation and facilitate commissioning and monitoring of the performance of FAAST LT Aspiration devices PipeIQLT provides a graphical interface o...

Page 10: ...puter in the normal way for your operating system Launching To launch the PipeIQLT application double click the PipeIQLT icon on the desktop Or click Start bottom left corner of the Windows screen and...

Reviews: