Product Overview: 

The 

Pertronic 

Indicating Manual Call-Point is a high-reliability conventional Fire Alarm activation 

device with a compact, aesthetically pleasing, low profile design. 
 

Features: 

- High reliability Fire Alarm activation device. 
- Safe Secure Commissioning without the need to remove the Snapglaze. 
- Push button latching switch with inbuilt LED indicator. 
- Can be installed into a standard single gang flush box fitting. 
- Low Profile Design. 
- Electronic components protected from damage. 
- ‘Snapglaze’ frangible element for improved user safety (Patent NZ Number: 272427). 
- Terminals accept 0.5mm2 to 1.5mm2 cables. 
- Bi-directional circuit connection terminals 
- The MCP clamps the circuit voltage at 2.3Vdc 
- Compatible with 12V Bell reversal of F4-2W and F1-2W systems. 
- For non-2W panels, reversal of the MCP causes a High Defect – the M-Level reached depends upon 
  the number of devices on the circuit and the number reverse-connected. 
- Fully complies with NZS 4512:2003 

 

Specifications: 

- Dimensions:  

 

115mm(height) x115mm(width) x 15mm(depth above flush-box) 
Designed to fit into a standard flush-box fitting 

- Electrical: 

 

Operating Voltage   

10 to 30Vdc 

Quiescent Current   

0mA 

Alarm Current  

 

Panel Dependent 

- MCP Indicators 

 

MCP Poll  

 

Switch Illuminates and flashes Red 

MCP Activated  

 

Switch Illuminates and latches Red 

- Environmental: 

 

Operating Temperature 

0 to 40

   Humidity 

  10 

to 

95% 

RH 

(non-condensing) 

 
Compatibility: 

Indicating Manual Call-Points are compatible with the following products: 

 
 

Product 

MCP Hardware Version

Panel Software Version

Release Date 

F1 

v1.0 & above 

v2.3 & above 

November 2003 

F1-2W 

v6.0 & above 

v9.04 & above 

March 2007 

F4 

v1.0 & above 

v2.26 & above 

November 2003 

F4-2W 

v6.0 & above 

v9.0 & above 

March 2007 

F16 

v1.0 & above 

v7.0 & above 

November 2003 

F16e 

v1.0 & above 

v1.10N & above 

June 2004 

Loop Responder  v1.0 & above 

v3.00N & above 

May 2004 

Apartment 
Module 

v1.2 & above 

v1.00N & above 

Feb 2006 