D.4.2.1 AC 3PH 380V (-15%)–440V (+10%)
Inverter model
Recommended
cable size
(mm
2
)
Size of connectable cable (mm
2
)
Terminal
screw
specifica
tion
Tighten
ing
torque
(Nm)
RST
UVW
PE
RST
UVW
P1, (+) PB, (+), (-)
PE
MSI350-1R5G-4
2.5 2.5 2.5–6 2.5–6 2.5–6 2.5–6 M4 1.2–1.5
MSI350-2R2G-4
2.5 2.5 2.5–6 2.5–6 2.5–6 2.5–6 M4 1.2–1.5
MSI350-004G-4
2.5 2.5 2.5–6 2.5–6 2.5–6 2.5–6 M4 1.2–1.5
MSI350-5R5G-4
2.5 2.5 2.5–6 2.5–6 2.5–6 2.5–6 M4 1.2–1.5
MSI350-7R5G-4
4 4 2.5–6 4–6 4–6 2.5–6 M4
1.2–1.5
MSI350-011G-4
6 6 4–10 4–10 4–10 4–10 M5 2.3
MSI350-015G-4
6 6 4–10 4–10 4–10 4–10 M5 2.3
MSI350-018G-4
10 10 10–16 10–16 10–16 10–16 M5 2.3
MSI350-022G-4
16 16 10–16 10–16 10–16 10–16 M5 2.3
MSI350-030G-4
25 16 25–50 25–50 25–50 16–25 M6 2.5
MSI350-037G-4
25 16 25–50 25–50 25–50 16–25 M6 2.5
MSI350-045G-4
35 16 35–70 35–70 35–70 16–35 M8 10
MSI350-055G-4
50 25 35–70 35–70 35–70 16–35 M8 10
MSI350-075G-4
70 35 35–70 35–70 35–70 16–35 M8 10
MSI350-090G-4
95 50 70–120 70–120
70–120
50–70 M12 35
MSI350-110G-4
120 70 70–120 70–120 70–120 50–70 M12 35
MSI350-132G-4
185 95 95–300 95–300 95–300
95–240
Nuts are used as
terminals, so it is
recommended that
you use a wrench
or sleeve.
MSI350-160G-4
240 120 95–300 95–300 95–300
120–240
MSI350-185G-4 95×2P 95 95–150 70–150 70–150 35–95
MSI350-200G-4 95×2P 120
95×2P
–150×2P
95×2P
–150×2P
95×2P
–150×2P
120–240
MSI350-220G-4 150×2P 150
95×2P –
150×2P
95×2P –
150×2P
95×2P –
150×2P
150–240
MSI350-250G-4 95×4P 95×2P
95×4P
–150×4P
95×4P
–150×4P
95×4P
–150×4P
95×2P
–150×2P
MSI350-280G-4 95×4P 95×2P
95×4P
–150×4P
95×4P
–150×4P
95×4P
–150×4P
95×2P
–150×2P
MSI350-315G-4 95×4P 95×4P
95×4P
–150×4P
95×4P
–150×4P
95×4P
–150×4P
95×2P
–150×2P
Summary of Contents for MSI350 Series
Page 1: ...MSI350 SERIES INVERTER USER MANUAL...
Page 2: ...2...
Page 34: ...34 4 2 6 Vertical installation Fig 4 5 Vertical installation...
Page 38: ...38 Fig 4 10 3PH 380V 30 37kW Fig 4 11 3PH 380V 45 110kW Fig 4 12 660V 22 45kW...
Page 39: ...39 Fig 4 13 660V 55 132kW Fig 4 14 380V 132 200kW and 660V 160 220kW...
Page 40: ...40 Fig 4 15 380V 220 315kW and 660V 250 355kW...
Page 71: ...71...
Page 83: ...83 When selecting customized V F curve function users can set the reference channels and...
Page 90: ...90...
Page 96: ...96...
Page 101: ...101...
Page 147: ...147...
Page 260: ...260 7 6 Analysis on common faults 7 6 1 Motor fails to work...
Page 261: ...261 7 6 2 Motor vibrates...
Page 262: ...262 7 6 3 Overvoltage...
Page 263: ...263 7 6 4 Undervoltage...
Page 264: ...264 7 6 5 Unusual heating of motor...
Page 265: ...265 7 6 6 Inverter overheating...
Page 266: ...266 7 6 7 Motor stalls during ACC...
Page 267: ...267 7 6 8 Overcurrent...
Page 336: ...336 A 6 5 PROFINET communication card EC TX509...
Page 380: ...380...
Page 386: ...386...
Page 387: ...387...
Page 388: ...388...