272
(5) Check 1PH powered devices, and ensure that no earth lines are used as neutral wires by these
devices.
(6) Do not use shielded cables as inverter power cables and motor cables.
7.7.5
Live device chassis
Phenomenon
After an inverter is started, there is sensible voltage on the chassis, and you may feel an electric shock
when touching the chassis. The chassis, however, is not live (or the voltage is far lower than the human
safety voltage) when the inverter is powered on but not running.
Solution
1. If there is power distribution grounding or ground stud on the site, ground the cabinet chassis of
the drive system through the power ground or stud.
2. If there is no grounding on the site, you need to connect the motor chassis to the ground terminal
PE of the inverter, and ensure that the jumper at "EMC/J10" on the middle casing of the inverter
is shorted.
Summary of Contents for MSI350 Series
Page 1: ...MSI350 SERIES INVERTER USER MANUAL...
Page 2: ...2...
Page 34: ...34 4 2 6 Vertical installation Fig 4 5 Vertical installation...
Page 38: ...38 Fig 4 10 3PH 380V 30 37kW Fig 4 11 3PH 380V 45 110kW Fig 4 12 660V 22 45kW...
Page 39: ...39 Fig 4 13 660V 55 132kW Fig 4 14 380V 132 200kW and 660V 160 220kW...
Page 40: ...40 Fig 4 15 380V 220 315kW and 660V 250 355kW...
Page 71: ...71...
Page 83: ...83 When selecting customized V F curve function users can set the reference channels and...
Page 90: ...90...
Page 96: ...96...
Page 101: ...101...
Page 147: ...147...
Page 260: ...260 7 6 Analysis on common faults 7 6 1 Motor fails to work...
Page 261: ...261 7 6 2 Motor vibrates...
Page 262: ...262 7 6 3 Overvoltage...
Page 263: ...263 7 6 4 Undervoltage...
Page 264: ...264 7 6 5 Unusual heating of motor...
Page 265: ...265 7 6 6 Inverter overheating...
Page 266: ...266 7 6 7 Motor stalls during ACC...
Page 267: ...267 7 6 8 Overcurrent...
Page 336: ...336 A 6 5 PROFINET communication card EC TX509...
Page 380: ...380...
Page 386: ...386...
Page 387: ...387...
Page 388: ...388...