202
P09.06
Derivative time
(Td)
It determines the intensity of the regulation made on
the change rate of deviation between PID feedback
and reference by PID regulator. If feedback changes
by 100% during this period, the regulation of
differential regulator (ignoring integral and differential
actions) is Max. output frequency (P00.03)
The longer the derivative time, the stronger the
regulation intensity.
Setting range: 0.00–10.00s
0.00s
○
P09.07
Sampling cycle
(T)
It means the sampling cycle of feedback. The regulator
operates once during each sampling cycle. The larger
the sampling cycle, the slower the response.
Setting range: 0.001–10.000s
0.001s
○
P09.08
Limit of PID
control deviation
It is the max. allowable deviation of PID system output
value relative to closed-loop reference value. Within
this limit, PID regulator stops regulation. Set this
function code properly to regulate the precision and
stability of PID system.
Setting range: 0.0–100.0%
0.0%
○
P09.09
Upper limit value
of PID output
These two function codes are used to set the
upper/lower limit value of PID regulator.
100.0% corresponds to Max. output frequency (P00.03)
or max. voltage (P04.31)
Setting range of P09.09: P09.10–100.0%
Setting range of P09.10: -100.0%–P09.09
100.0%
○
P09.10
Lower limit value
of PID output
0.0%
○
P09.11
Feedback offline
detection value
Set PID feedback offline detection value, when the
detection value is no more than the feedback offline
detection value, and the duration exceeds the value set
in P09.12, the inverter will report "PID feedback offline
0.0%
○
P09.12
Feedback offline
detection time
1.0s
○
Summary of Contents for MSI350 Series
Page 1: ...MSI350 SERIES INVERTER USER MANUAL...
Page 2: ...2...
Page 34: ...34 4 2 6 Vertical installation Fig 4 5 Vertical installation...
Page 38: ...38 Fig 4 10 3PH 380V 30 37kW Fig 4 11 3PH 380V 45 110kW Fig 4 12 660V 22 45kW...
Page 39: ...39 Fig 4 13 660V 55 132kW Fig 4 14 380V 132 200kW and 660V 160 220kW...
Page 40: ...40 Fig 4 15 380V 220 315kW and 660V 250 355kW...
Page 71: ...71...
Page 83: ...83 When selecting customized V F curve function users can set the reference channels and...
Page 90: ...90...
Page 96: ...96...
Page 101: ...101...
Page 147: ...147...
Page 260: ...260 7 6 Analysis on common faults 7 6 1 Motor fails to work...
Page 261: ...261 7 6 2 Motor vibrates...
Page 262: ...262 7 6 3 Overvoltage...
Page 263: ...263 7 6 4 Undervoltage...
Page 264: ...264 7 6 5 Unusual heating of motor...
Page 265: ...265 7 6 6 Inverter overheating...
Page 266: ...266 7 6 7 Motor stalls during ACC...
Page 267: ...267 7 6 8 Overcurrent...
Page 336: ...336 A 6 5 PROFINET communication card EC TX509...
Page 380: ...380...
Page 386: ...386...
Page 387: ...387...
Page 388: ...388...