background image

6

 

 

 

Pump breakdown: 

If the circulator stops, the system goes into alarm and 

stops (Er01, Er04).

 

 

Ignition  failed: 

The  system  has  1  ignition  attempt,  if  it  is  not  successful 

the boiler goes into a safe state then in BLOCK (Er12). Before each igni-

tion, the brazier self cleans, in case of self

-

cleaning failure the system will 

go into error Er25.

 

 

Electrical  protection: 

The  system  is  protected  with  a  4  A  fuse  that  is 

located on the back of the stove. To replace it, extract the tray next to the 

switch  only  after  disconnecting  the  power  cable  from  the  power  supply, 

replace the broken fuse and reinsert the tray, if the new fuse immediately 

breaks, contact a technician.  

 

 

Exhaust  fume  safety: 

If there  are  any  anomalies  with  the smoke expul-

sion from the system, an alarm will go off and the system will block (Er02). 

 

 

Pellet  safety: 

If the temperature inside the pellet tank exceeds the safety 

level, the system blocks (Er01). The reinstatement is automatic,

 

 

Water  temperature  safety: 

In  case  the  water  temperature  in  the  boiler 

exceeds the safety level, the system goes into block (Er01). The reinstate-

ment is manual and must be carried out by a qualified technician by pres-

sing the reset button behind the boiler.  

 

 

Water  pressure  safety: 

The  pressure  of the system  is controlled by  an 

electronic pressure transducer and must be in between 0.2 bar (200 mbar) 

and 2,8 bar (2800 mbar), se non sono rispettate le condizioni, il sistema va 

in blocco (Er09 o Er10), if these conditions are not complied with the sy-

stem  goes  into  block  (Er09  or  Er10).  If  the  system  goes  over  3  bar,  an 

automatic  safety  valve  opens  and  releases  the  excessive  pressure.  To 

regulate the pressure within the function range, adjust the discharge valve 

behind the boiler or on the radiator.

 

 

Power  failure: 

If  there  is  a  short  power  failure  in  the  power  supply,  the 

system will go into BLOCK (Er15). If the lack of electricity is not brief, the 

boiler could release a small quantity of smoke in the room, if the air intake 

has  not  been correctly connected  to  the  outside. 

This is  caused by  the 

scarce draw of the chimney flue and does not represent any risk for 

one

s safety. 

When the power comes back, the system switches itself off.  

 

Warning: In the case the chimney catches fire, call the fire brigade. 

 

 

MINIMUM SAFETY DISTANCES

 

 

Keep  fuels  and  flammable  substances  at  an  adequate  distance  from  the 

stove. For minimum distances from flammable materials, one can refer to 

the products identification plate located on the back of the stove.

 

 

Caution:  Some  models  could  have  minimum  safety  distances  diffe-

rent  from  dimensions  shown  below,  therefore  it  is  strongly  recom-

mended checking always the idenditication plate located on the back 

of the stove to make sure the values of minimum safety distances.

 

 

Connecting to a system with zone valves

 

Leave at least one zone always open. We recommend installing an anti

-

condensation valve at 55 °C (mandatory in the case of direct connection 

to the system).

 

 

WARNING: the boiler must be installed on a properly sized system 

to dispose of the power generated by the appliance. For the sizing 

of the system it is recommended to rely on a thermo technician.

 

 

To  dissipate  excess  heat,  the  boiler must  be connected  to  at least  two 

radiators. The system drain valve and the safety valve are on the back of 

the boiler, they must both be connected to a drain well according to the 

regulations in force.

 

 

Hot water production kit (optional)

 

 

On the boiler it is possible to install a kit on board of the 

appliance  for  the  production  of  hot  water.  This  optional 

feature  provides  unmatched  comfort  because  everything 

is completely automatic and controlled by the control unit.

 

Note: 

The kit must be connected to the hydraulic system 

in accordance with its input and output indications, the maximum admis-

sible pressure is 2 bars (this operation must be carried out by a qualified 

technician).

 

Long

-

term non

-

use conditions

 

 

If the hydro stove has not been used for a long period of time, it is rec-

ommended  to  contact  a  qualified  technician  to  carry  out  the  following 

operations: 

 

 

-

  Apply adequate antifreeze according to the area where it is located

 

 

-

  Place the switch in the 

1

 position

 

 

-

  Close all the valves of the heating and domestic water system

 

 

Operating Conditions

 

 

The boiler has been designed to be used in ordinary environments, whe-

re  there  is  no  danger  of  fire  or  explosion.  The  disposal  of  combustion 

waste must be carried out in accordance with the applicable legal provi-

sions.

 

When  using  the  boiler,  the  settings  of  the  safety  devices  or  the  fixed 

guards  can  not  be changed.  The  control  devices must  be  regulated  by 

qualified technicians.

 

Maintenance of the boiler must be carried out by specialized companies 

in the maintenance of heating appliances, which will subject it to all the 

checks required by current regulations.

 

Use  wood  pellets  with  a  diameter  of  6mm,  average 

length of 30mm, with humidity characteristics in com-

pliance  with  the  EN  PLUS

-

UNI  EN  14961

-

2  standard, 

class A1. Store the fuel in a cool, dry place away from 

heat sources.

 

Caution: The boiler modified or equipped with special 

applications must undergo a new conformity check. The incorrect 

connection of the boiler to the chimney and failure to comply with 

the provisions regarding the construction of the ventilation ope-

nings can cause serious dangerous situations.

 

 

Residual risks

 

 

Some parts, for example the smoke outlet, during operation may be very 

hot to the touch and cause burns. The electrical parts can cause serious 

damage, do not touch these parts without having disconnected the 

mains cable from the mains.

 

 

SAFETY DEVICES

 

 

Breakage of the exhaust fan: 

If for any reason the fan breaks, a safety 

measure intervenes and blocks the pellet flow (Er02), an alarm goes off 

and stops the stove

s function.  

 

Breakage  of  the  auger  motor: 

If the auger motor stops feeding pellet, 

the  system  still  continues  to function  on minimum  levels then  an  alarm 

goes off and the stove blocks (Er12, Er03).

 

 

 

 

Note: 

The stove can be installed close to a not flammable material wall, 

as long as electronic devices and electrical connections will be accessi-

ble and there will be enough space for maintenance

 

 

Distance in mm

 

EN

 

Summary of Contents for ALADINO

Page 1: ...1 USER MANUAL Installation use and maintenance ALADINO CLESSIDRA ELEGANCE ERGONOMIC PRESTIGE TURBO TOP TURBO GLASS TURBO COMPACT VISION SLOT VISION DOLBY TECNIKA FOR HOME TECNIKA GLASS 2022 AQUA Off...

Page 2: ...tting COMBUSTION Automatic combustion regulation by FCS Calibration FIRE PROTECTION TOUCH DISPLAY RADIO DISPLAY Introduction Button description OPERATING STATUS Check Up Ignition Normal Modulation Com...

Page 3: ...horough reading of the user and maintenance manual and scru pulously observe the indications and signs located on the hydro stove The plug of the power cable must be connected only AFTER the installa...

Page 4: ...ation in small rooms or bedrooms can take place only if the stove is her metic hermetic system and air required for the combustion must be drawn directly from the outside through a tube All local regu...

Page 5: ...CURVE PROTECTION CAP INSULATED FLUE ASH DEPOSIT IN THE CURVE CHIMNEY FLUE INSIDE AN OLD CHIMNEY CORRECT INSTALLATION CHIMNEY WITH COVER PLATE INSULATION OPEN 45 CURVE OLD CHIMNEY FLUE T WITH INSPECTIO...

Page 6: ...the boiler straight under the power connector it has a two pin connector coupling with two buttons one black and one red The connection to the thermo stat assures the function that the boiler can go i...

Page 7: ...a properly sized system to dispose of the power generated by the appliance For the sizing of the system it is recommended to rely on a thermo technician To dissipate excess heat the boiler must be co...

Page 8: ...to check the quality of the flame by comparing it to the images in the examples above since certain conditions of use and installation could in any case lead to machine malfunctions In any case in th...

Page 9: ...used to avoid them Owners managers and users of buildings and facilities must ensure the safety of people animals and objects Owners managers and users of buildings and facilities are responsible for...

Page 10: ...h your finger and swipe vertically Press to Confirm Press to Cancel Press to Edit Press to go back to the previous page Press to go back to the Homepage To unlock the standby screen press on the displ...

Page 11: ...eful Hydraulic System Configuration P26 2 3 10 11 are active The Maximum value can be programmed by setting Thermostat Th83 Delivery Thermostat It can be viewed if the Return Delivery Probe and the us...

Page 12: ...e or deactivate the automatic burn pot cleaning system this process takes place during the ignition phase It is recommended to keep it activated Mixing Valve It appears only if an output is configured...

Page 13: ...ect the day of the week you want to program press on the on off times and scroll up or down to change them There are 3 time slots for each day Brightness Minimum Brightness Standby display Control pan...

Page 14: ...ed with a and the rela tive error code Select between the periods Monday Friday and Saturday Sunday There are 3 phases for Monday Friday and 3 phases for Saturday Sunday The three types of programs ar...

Page 15: ...seconds P6 Decrease power Scroll through Menu Decrease parame ter values DESCRIPTION OF THE MENUS The boiler is equipped with various functions available in the individual programming menus Some of th...

Page 16: ...es use the keys P4 and P6 to increase or decrease the value and confirm the setting by pressing P3 Press P1 to exit the menu Chrono This menu allows you to set the switch on and switch off time slots...

Page 17: ...ch on the boiler using the Chrono function Tuesday Wednesday Thursday Friday Monday Weekly senai Week end Daily Monday ON OFF 00 00 00 00 V 00 00 00 00 00 00 00 00 Mon Sun ON OFF 00 00 00 00 V 00 00 0...

Page 18: ...lows you to read the system error list Attention to be used only by an authorized MORETTI DESIGN techni cian Auger Calibration This item allows you to adjust auger rotation speed Attention to be used...

Page 19: ...Room Temperature measured by the remote Chrono Activation Current time Descrizione Tasti Tasto Funzione Descrizione Sleeping Mode By pressing the button when the main screen is displayed the radio dis...

Page 20: ...t is possible to change the combustion power level at any time but the change is effective only during Normal mode The power level ranges from 1 to 5 Increasing the power level increases the pellet co...

Page 21: ...e items of the menu use the keys To confirm the data press SET To exit press ESC Daily Select the day of the week you want to program and set the switch on and switch off times There are 3 time slots...

Page 22: ...T Recipe Power Thermostats Chrono Settings Informations Radio Standby Menu to switch off the radio display completely To switch on the radio display again To reactivate the remote control press first...

Page 23: ...t Key Tone Date and Time Secondary Information This menu allows you to view some of the system operating para meters To scroll through the menu use the keys press ESC to exit Radio Test This menu allo...

Page 24: ...ower Thermostats Chrono Information Settings Service WiKey Thermostat Secondary Information Radio Test Change Code Reset Cleaning Screw Feeder Calibra Screw Feeder Calibration Max 7 Set 0 Min 7 Automa...

Page 25: ...e available values E g 1 2 3 Minimum Average Maximum After 3 seconds the value is saved and the normal display reappears WIFI CONFIGURATION To configure thermo stoves equipped with a WiFi module it is...

Page 26: ...If the domestic hot water kit is installed it is not necessary to change the setting on the hydro stove Connections on the control unit Connections on the heating system the following figure is only...

Page 27: ...s the hydro stove Boiler Probe S the hydro stove Pump P1 Valve P2 Boiler Puffer Probe S3 Electrovalve P2 17 towards heating system 18 towards domestic hot water Probe ACS DHW S3 17 vers l installation...

Page 28: ...tem includes the hydro stove Boiler Probe S1 the hydro stove Pump P1 Boiler Puffer Probe S1 the heating system pump Pump P2 Probe Puffer Boiler S1 Probe Puffer Boiler S1 Pump P2 For models ALADINO ELE...

Page 29: ...s only illustrative The system includes the hydro stove Boiler Probe S1 the hydro stove Pump P1 Boiler Puffer Probe S1 the heating system pump Pump P2 For models ALADINO ELEGANCE CLESSIDRA ERGONOMIC C...

Page 30: ...uffer Probe S1 Electrovalve P2 DHV probe S3 17 towards heating system 18 towards domestic hot water Electrovalve Probe S1 Puffer Boiler Pump P3 For models ALADINO ELEGANCE CLESSIDRA ERGONOMIC COMPACT...

Page 31: ...Pump P1 heating system Pump P3 Puffer Probe S1 Electrovalve P2 DHV probe S3 Electrovalve P2 Probe S1 Puffer Boiler Pump P3 17 towards heating system 18 towards domestic hot water For models ALADINO EL...

Page 32: ...be installed according to standard regulations and directions contained in this manual PRESSURE SWITCH BROKEN Unblock and turn on the stove if the error occurs immediately it is likely that the pressu...

Page 33: ...echnician Er11 The error occurs due to problems with the internal clock CLOCK ERROR Turn off the main switch reset the time and date page 11 then unblock If the error persists replace the battery on t...

Page 34: ...front door or open pellet door FRONT DOOR OR PELLET DOOR OPEN FOR MORE THAN 120 SE CONDS Unlock and check if the doors have been closed correctly If the error persists contact an authorised technician...

Page 35: ...IN11 Input IN12 Input IN11 Storage Tank Probe Flowmeter Room Thermostat OPTIONAL Limit Switch Micro Burn Pot Cleaning ALL CLEAN MODELS ONLY Flowmeter Sensor Pressure Sensor Combustion Fan Encoder Wat...

Page 36: ...35 Remote Control Cod PSYSI04000005 Off Output to be configured Output to be configured Output to be configured Output to be configured ELECTRONIC CONTROL UNIT Code PSYSS04000003 EN...

Page 37: ...I FI 4HEAT system Code PSYSF09000002 EN LINE Combustion Fan Burn Pot Cleaning Motor Tube Bundle Cleaning Motor Spark plug Screw Feeder Safety Thermostat Pressure Switch Pump Tube Bundle Cleaning Motor...

Page 38: ...e Exaust Probe 32 Rosso 33 IN2 Auger Motor Encoder 34 GND 35 IN3 Micro Switch Pellet door and Front door 36 GND 37 IN4 Water probe 38 GND 39 IN5 Encoder Sensor Exaust Ventilator 40 GND 41 V 42 Vc Flow...

Page 39: ...e diluents can damage the stove s surfaces To ensure that the hydro stove always has an optimal combustion and to avoid malfunctions frequent cleaning operations must be carried out The frequency of t...

Page 40: ...EV 07 2022 ENG Moretti Fire s r l ITALY www morettidesign it The Moretti fire s r l assumes no responsibility for any errors in this manual and the right to modify without notice features of its produ...

Reviews: