www.miinet.com
Moore Industries-International, Inc.
- 13 -
User’s Manual
235-781-00D
June 2019
T2X RTD Temperature Transmitter
T2X
Installation of LH Enclosure Apparatus
1. Install the LH2 enclosure onto a surface, temperature thermowell, or onto a standard 2-inch pipe using the
mounting hardware. Remove the cap from the LH2 by rotating the cap counter clockwise after unlocking by
rotating the locking screw clockwise.
2. Connect input and output wiring in accordance with the connection information found in the User’s Manual
for that instrument.
3. Replace the cap to the LH2 by rotating the cap clockwise. Secure (lock) the cap by rotating the locking
screw counterclockwise.
4. Connect a ground wire between the ground screw on the LH2 enclosure to an appropriate earth ground.
Figure 4. Installation dimensions for LH2 enclosure
.
30 mm
(1.2 in)
DIA.
72 mm
(
DIA
.
2.85 in)
9 mm
(0.35 in)
87 mm
(3.44 in)
Conduit
Entry Port
Instrument
Mounting Holes
40 mm (1.56 in)
Instrument
Mounting
Holes
33 mm
(3.07 in)
I.D. 62 mm x 19 mm Deep
(I.D. 2.43 in x 0.76 in
)
Ground
M4.0 x 0.7
(4 Places)
89 mm
(3.5 in)
84 mm
(3.30 in)
CL
61 mm
(2.4 in)
2-in Pipe Bracket
Mounting Holes (4)
61 mm
(2.4 in)
92 mm
(3.61 in)
Process Connection
1/2-in NPT (N and M models) or
G½ (BSP) (C models)
61 mm
(2.4 in
)
10-32
Mounting
Holes (2
)
51 mm
(2.0 in)
Safety Lock
(LH2 only)
Metal Tag
2-INCH PIPE MOUNTING HARDWARE
BOTTOM
INSIDE
SIDE
FRONT