Moore Industries TEMPTATION 2000 T2X User Manual Download Page 8

www.miinet.com

Moore Industries-International, Inc.

- 8 -       

User’s Manual

235-781-00D

June 2019

T2X RTD Temperature Transmitter

T2X

1.   Selecting Input Type, Wiring, etc.

 

Use the selection tools in the “Input Type” box to choose the sensor type that the T2X will be reading.  Select 

the appropriate “Input Type” values.  Continue to change the remaining areas in “Input Type”, such as ohms 

and # wires, until the entire “Input Type” area matches the desired parameters for your transmitter.

2.   Scaling the Input & Setting the Reverse Output

 

Scaling the input allows you to set the T2X to scale its output in response to a portion of the total range of the 

selected input type.  In a reverse output application, the T2X output drops in proportion to a rise on input, and 

rises in proportion to a drop in the input.

 

  

To scale the input:  

To set the scaling, select the “Input Zero” box and enter the value for the desired Input 

Zero from the application where the T2X is to be employed.  Select the “Input Full” box and enter the value 

for the desired Input Full.

 

 

To set reverse output:

  Follow the instructions to scale the input, but enter a value in the “Input Zero” box that 

is greater than the Input Full, and a value in the “Input Full” box that is less than the Input Zero.

 

3.   Scaling the Output

 

The T2X can be configured to scale its 4-20mA output to offset the performance or 

 

calibration of other instruments in the process loop. To scale the output, enter the desired Output Zero value 

in the “Zero Scale Output” box, or use the slide bar to adjust the value.  Select the “Full Scale Output” box 

and enter the desired Output Full value.

4.   Setting Miscellaneous Functions

 

There are several radio buttons on the T2X Configuration Program Main Screen that 

 

control additional transmitter functions. 

 

Setting Engineering Unit Readout: 

 Use this setting to have the Configuration Program calculate the 

 

Centigrade or Fahrenheit temperature for readout in the “Status” area of the screen.

 

 

Setting Input Filtering:

  Use this radio button setting to filter out noise from the power to the transmitter.

 

 

Choosing Between Upscale and Downscale Drive: 

 This button configures the 

 

transmitter to drive its output either up to 24mA or down to 3.3mA when a sensor or sensor wiring failure is 

detected.

 

 

5.   Enabling/Disabling Broken Wire Detection

 

During operation, the T2X sends random micro-amp pulses through input wiring to check for broken wiring or 

a burned-out sensor. This can cause problems with temperature calibrators.  To turn this feature off, set the 

“Calibration” radio button to “Calibration Mode”.

 

6.   Downloading your new T2X Settings

 

To start the download process, click on the “Stop/Start” button at the bottom of the screen, then on the “Prog” 

button.  This transfers the settings from the software to the memory of the connected transmitter.

Summary of Contents for TEMPTATION 2000 T2X

Page 1: ...e m a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual T2X Temptation 2000 T2X RTD Temperature Transmitter No 235 781 00D Jun...

Page 2: ...the original sale www miinet com Demand Moore Reliability Locations World Headquarters Europe Australia 16650 Schoenborn Street North Hills California 91343 6196 U S A Tel 818 894 7111 Fax 818 891 28...

Page 3: ...re or condition that could injure the operator Qualified Personnel The Moore Industries product systems described in this manual may be operated only by personnel qualified for the specific task in ac...

Page 4: ...ng the T2X 6 Managing Configuration Files 7 Specifications 9 Accessories 9 Ordering Information 10 Installing and Connecting the T2X 11 Physical Instructions for Installing an Encapsulated Hockey Puck...

Page 5: ...e necessary equipment as listed in Table 1 installing the T2X PC Configuration Program onto your computer then connecting the T2X as shown in Figure 1 It is necessary to connect the T2X to the PC befo...

Page 6: ...T2X in the form of a configuration file Pages 7 8 of the manual contains all of the instructions for configuring the T2X Use Figure 2 to find the portion of the screen that you have a question about...

Page 7: ...o be saved and click Save Answer Yes to the dialogue box that pops up to finish saving the file Retrieving a Configuration File from Disk To retrieve a file click on the File button Use the display on...

Page 8: ...le its 4 20mA output to offset the performance or calibration of other instruments in the process loop To scale the output enter the desired Output Zero value in the Zero Scale Output box or use the s...

Page 9: ...ohms Recommended 35 ohms per wire for three wire inputs 5 ohms per wire for 10 ohm Cu inputs Damping 0 5 seconds user selectable Ambient Tem perature Operating Storage Range 40 C to 85 C 40 F to 185 F...

Page 10: ...ter cover LH2NS Explosion proof connection head with two entry ports inch NPT cable and process black metal cover LH2MS Explosion proof connection head with two entry ports M20 cable and inch NPT proc...

Page 11: ...that best suits your application 2 WIRE RTD or DECADE RESISTANCE BOX PS 2 3 4 1 PS POWER SOURCE 8 42Vdc CURRENT DRIVEN INSTRUMENT 3 WIRE RTD OR DECADE RESISTANCE BOX 4 WIRE RTD OR DECADE RESISTANCE BO...

Page 12: ...ocess Instrumentation Industry For 2 wire transmitters certified and intended to be operated as either Intrinsically Safe Non Incendive Class I Div 2 or Type N the power parameters are clearly stated...

Page 13: ...ng the cap clockwise Secure lock the cap by rotating the locking screw counterclockwise 4 Connect a ground wire between the ground screw on the LH2 enclosure to an appropriate earth ground Figure 4 In...

Page 14: ...to the receiving device see Note below Note Some of Moore Industries instruments can be classified as receivers IPT2 IPX2 etc and some can be classified as transmitters TRX TRY etc while some are both...

Page 15: ...ature Transmitter T2X This secti Locations Maximum 300uA an on contains im s m operating pa d 240uW mportant info arameters of t rmation regar the COM po rding installat ort for use in N tion of the T...

Page 16: ...D T6 Ta 60 C The T2X shall be installed in an enclosure meeting the requirements of ANSI ISA S82 02 01 or other applicable ordinary location standards No connections shall be made to the communicatio...

Page 17: ...Parameters can be found in Control Drawing 100 100 38 Non Incendive Applications Class I Division 2 Groups A D T6 Ta 60 C The model T2X is of open type unit Certified as a component for use only in o...

Page 18: ...www miinet com Moore Industries International Inc 18 User s Manual 235 781 00D June 2019 T2X RTD Temperature Transmitter T2X...

Page 19: ...No modifications are permitted without the notification and approval of the Q A Certification Engineer related dwgs or the Certifying Agency schedule dwgs 2 250 MODEL SERIAL TAG 1866A 2 S Class II II...

Page 20: ...This is a controlled Related or Schedule drawing No modifications are permitted without the notification and approval of the Q A Certification Engineer related dwgs or the Certifying Agency schedule...

Page 21: ...NOTICE RE PROPRIETARY INFORMATION This drawing and the information contained herein are the proprietary property of Moore Industries International Inc MIi and should not be reproduced or disclosed to...

Page 22: ...l or workmanship This policy extends to the original Buyer only and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall e...

Reviews: