T2X RTD Temperature Transmitter
T2X
Specific Conditions of Use
The following instructions must be adhered to when the T2X is used in hazardous locations and potentially
explosive atmospheres.
cFMus Installations
Intrinsically Safe Applications
Class I,II,III, Division 1, Groups A-G T6 Ta = 60°C
Class I, Zone 0 AEx ia IIC T6 Ta = 60°C
The T2X shall be installed in an enclosure meeting the requirements of ANSI/ISA S82.02.01 or other
applicable ordinary location standards.
No connections shall be made to the communications “COM” port in Hazardous (Classified) Locations.
Entity Parameters can be found in Control Drawing 100-100-38 included in this manual.
Nonincendive Applications
Class I Division 2, Groups A-D T6 Ta = 60°C
The T2X shall be installed in an enclosure meeting the requirements of ANSI/ISA S82.02.01 or other
applicable ordinary location standards.
No connections shall be made to the communications “COM” port in Hazardous (Classified) Locations.
European Union Installations
(ATEX 2014/34/EU Directive)
Intrinsically Safe Applications – Category 2G
II 2 G EEx ib IIB T6
The apparatus is intrinsically safe. It can be used in potentially explosive atmospheres. The equipment must
only be associated with certified intrinsically safe associated apparatus and these combinations must be
compatible as regards intrinsic safety
The electrical parameters of the certified associated intrinsically safe apparatus must not exceed any of the
following values : (terps, -ps) Uo ≤ 30V; Io ≤ 110mA; Po ≤ 0.82W
The “COM” port must not be used in a hazardous area.
Operating ambient temperature: -40°C to +60°C
The specific parameters of the mode(s) of protection can be found in Control Drawing 100-100-38 in this
manual.