Moore Industries IPT2 User Manual Download Page 9

IPT

  

2

 

The Interface Solution Experts 

9

Installation

Installation of the IPT

2

 is divided into three phases:  

mounting, electrical connections, and pneumatic con-
nections.  In most cases, it is easier to mount the IPT

2

 

before completing the electrical and pneumatic con-
nections.

Mounting

Individual IPT

2

s consist of two parts: the transmitter 

and the mounting block.  Units without a mounting 
block snap onto a header.  IPT

2

s with a mounting block 

are rail mounted.  Ensure that the unit is mounted in 
an area free of dust, moisture, and corrosive elements.  
See Figure 4 for mounting dimensions.

Note:

It is recommended that mounting blocks and headers 

be purged of any debris prior to mounting the IPT 

2

.  In-

sert a small diameter, blunt tip probe into the fi tting and 

unseat the ball-check valves for a few minutes with the 

fi ltered instrument air supply in operation.

Rack- or surface-mounted  IPT

2

s should be ordered 

with a Moore Industries' rack-mounted header (RIR) or 
a surface-mounted header (SIR).  This eliminates the 
need for an interlocking mounting block and rail.   5, 10 
or 15 units can be snapped onto one header, allowing 
multiple units to receive supply air from one supply 
pipe.  To mount an IPT

2

 onto a header, push the unit 

into place until the retaining lever snaps up fl ush be-
neath the handle.  To remove an IPT

2

, press down on 

the retaining lever and lift the unit out by the handle.

Note:

Check valves in the headers prevent the loss of 

supply or output air during mounting or removal 

of IPT 

2

s. 

Rail-mounted  IPT

2

s must use a pneumatic mounting 

block. Pneumatic mounting blocks are 1.39 inches 
wide.  Using a 0.17 inch wide gauge between blocks 
provides uniform spacing while occupying minimum 
rail length.

Caution:

Coupler must be kept lubricated to prevent 

damage to O-rings in test jacks.  Te

fl

 on 

lubricant is recommended.  If grease is used, 

keep out of air passage.

If the unit is not supplied with the output test jacks, use 
an air pressure gauge to measure the output air supply 
pressure (e.g., read 3psig for a 3-15psig unit or 15psig  
for a 15-3psig unit).

 

4.  Any deviation in the output pressure (e.g., 3 psig 

for a 3-15 psig unit or 15 psig for a 15-3 psig unit), 
can be corrected by using the Zero potentiomenter 
in a range of ±10%.

5.  Set the current input signal for 100 percent output 

(e.g. 20mA for a 4-20mA input, 3-15psig output; 
4mA for a 4-20mA input, 15-3psig reverse output).

6.  Any deviation in the output pressure (e.g., 15 psig 

for a 3-15 psig unit or 3 psig for a 15-3 psig unit), 
can be corrected by the Span potentiometer over 
the range of ±10%.

7.    Repeat steps 1 through 6 (as applicable) until no 

further adjustments are required.

Summary of Contents for IPT2

Page 1: ...IPT2 IPT 2 July 2016 170 730 00G Current to Pressure I P Transmitter All product names are registered trademarks of their respective companies Current to Pressure I P Transmitter...

Page 2: ...Information 5 Application Information 6 Calibration 7 Adjustments 7 Calibration Equipment 7 Test Jacks 8 Calibration Setup 8 Calibration Procedure 8 Installation 9 Mounting 9 Installation in Hazardou...

Page 3: ...r documentation is missing this number is used to identify equipment characteristics The model number for the IPT2 is located on a label on the side of the unit Serial Number Moore Industries maintain...

Page 4: ...FA11 FA12 See Table 1 for more information Housing DIN Aluminum DIN style housing assembly WTI Rain proof as de ned by NEMA 3R FA7 or FA8 required WTIP Rain proof as de ned by NEMA 3R with plate and...

Page 5: ...on temperature pressure and the relative humidity of the air Su cient water must be removed to lower the dew point of the air to a temperature below ambient The dew point at line pressure is expressed...

Page 6: ...on to prevent oil contamination of the desiccant as well as downstream ltration to prevent desiccant nes from introducing new contamination The service life of an IPT2 is directly proportional to the...

Page 7: ...he wiper stop Usually a slight change can be felt when the clutch is at the end of a range i e it is slipping However if this change is not felt either end can be reached by turning the shaft 15 turns...

Page 8: ...illustration of a typical calibration setup including optional equipment To check or calibrate the IPT2 connect the unit as shown in this illustration Calibration Procedure There are two options show...

Page 9: ...the unit into place until the retaining lever snaps up ush be neath the handle To remove an IPT2 press down on the retaining lever and lift the unit out by the handle Note Check valves in the headers...

Page 10: ...be used when the IPT2 is installed in a Class I Division 2 location Australia New Zealand ANZEx Installations Certi cate No ANZEx 09 3000X Nonincendive Type n application Ex n Marking Code Ex n IIC T6...

Page 11: ...D for 2mm 0 8 in Dia Phone Tip Plug Used in FA3 FA4 FA8 FA10 FA11 and FA12 IPT CURRENT PRESSURE TRANSMITTER IN IN SPAN ZERO 39mm 1 54 in 2 Zero Adj Span Adj T T Pneumatic Test Jack Used in options FA3...

Page 12: ...ibed in the Maintenance section Operation Reverse output operation Once adjusted and installed the IPT2 operates unattended except for occasional cleaning of the air supply lters If a malfunction is i...

Page 13: ...ly and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall no...

Reviews: