Moore Industries IPT2 User Manual Download Page 10

IPT

  

2

10 

The Interface Solution Experts

Installation in Hazardous 
Locations 

This section contains important information regarding 
installation of the IPT

2

 in Hazardous Area Locations. 

This equipment is suitable for use in Class I, Division 
2, Groups A, B, C & D or non-hazardous locations 
only. Field wiring shall be rated for 85˚C.

WARNING: 

Explosion Hazard. Do not disconnect 

equipment when a fl ammable or combustible 
atmosphere is present.  

AVERTISSEMENT: 

Risque d’explosion. Ne pas 

débrancher tant que le circuit est sous tension, 
a moins qu’il ne s’ agisse d’un emplacement non 
dangereux.

WARNING: 

Explosion Hazard. Substitution of 

components may impair suitability for Class I, 
Division 2.

AVERTISSEMENT: 

Risque d’explosion. La substitution 

de composants peut rende ce materiel inacceptable 
pour les emplacements de Classe I, Division 2.

WARNING:

 Explosion Hazard. Test Jacks (-T and 

+T) shall not be connected or disconnected when a 
fl ammable or combustible atmosphere is present.

Special Conditions of Use 

The following instructions must be adhered to when 
the IPT

2

 is used in hazardous locations and potentially 

explosive atmospheres.

The IPT

2

 shall be installed in compliance with the 

enclosure, mounting, spacing and segregation 
requirements of the ultimate application.

The IPT

2

 shall be mounted in a tool secured enclosure 

when installed in a Class I, Division 2 location.

The test jacks (-T and +T) shall not be used when the 
IPT

2

 is installed in a Class I, Division 2 location.

Australia New Zealand ANZEx 
Installations

Certifi cate No.: ANZEx 09.3000X

Nonincendive, Type n application (Ex n)
Marking Code: Ex n 

II

C T6@55°C

Maximum Input Voltage Ui 30V
Maximum Input Current 

I

i 110mA

Standards:
AS/NZS 60079.0:2005 Explosive atmospheres - 
Equipment - General requirements 

AS/NZS 60079.15:2006 Explosive atmospheres - 
Equipment protection by type of protection ‘n’

Electrical Connections

The electrical connections are made to the removable 
terminal blocks located on the front of the unit.  There 
are two terminals on the IPT

2

 for connecting input 

current.  

The electrical terminals are compression screw 
sockets that accept 22 to 14 AWG hookup wire.  To 
complete these connections, use a slotted screwdriver 
with a head approximately 0.125 inch (3mm) in width 
to secure the wire leads to the transmitter.  Loosen 
each screw prior to inserting the wire being terminated.  
Strip and then tin the end of each wire with 60/40 
solder.  Then, while holding the uninsulated end of the 
wire in place, tighten the screw of the corresponding 
terminal.

Recommended Ground Wiring Practices

Moore Industries recommends the following ground 
wiring practices:

  •  Any Moore Industries product in a metal case  
     or housing should be grounded.

  •  The protective earth conductor must be connected        
     to a system safety earth ground before making      
     other connections.

  •  All input signals to, and output signals from, Moore      
     Industries’ products should be wired using a             
     shielded, twisted pair wiring technique.  Shields  
     should be connected to an earth or safety ground.

Summary of Contents for IPT2

Page 1: ...IPT2 IPT 2 July 2016 170 730 00G Current to Pressure I P Transmitter All product names are registered trademarks of their respective companies Current to Pressure I P Transmitter...

Page 2: ...Information 5 Application Information 6 Calibration 7 Adjustments 7 Calibration Equipment 7 Test Jacks 8 Calibration Setup 8 Calibration Procedure 8 Installation 9 Mounting 9 Installation in Hazardou...

Page 3: ...r documentation is missing this number is used to identify equipment characteristics The model number for the IPT2 is located on a label on the side of the unit Serial Number Moore Industries maintain...

Page 4: ...FA11 FA12 See Table 1 for more information Housing DIN Aluminum DIN style housing assembly WTI Rain proof as de ned by NEMA 3R FA7 or FA8 required WTIP Rain proof as de ned by NEMA 3R with plate and...

Page 5: ...on temperature pressure and the relative humidity of the air Su cient water must be removed to lower the dew point of the air to a temperature below ambient The dew point at line pressure is expressed...

Page 6: ...on to prevent oil contamination of the desiccant as well as downstream ltration to prevent desiccant nes from introducing new contamination The service life of an IPT2 is directly proportional to the...

Page 7: ...he wiper stop Usually a slight change can be felt when the clutch is at the end of a range i e it is slipping However if this change is not felt either end can be reached by turning the shaft 15 turns...

Page 8: ...illustration of a typical calibration setup including optional equipment To check or calibrate the IPT2 connect the unit as shown in this illustration Calibration Procedure There are two options show...

Page 9: ...the unit into place until the retaining lever snaps up ush be neath the handle To remove an IPT2 press down on the retaining lever and lift the unit out by the handle Note Check valves in the headers...

Page 10: ...be used when the IPT2 is installed in a Class I Division 2 location Australia New Zealand ANZEx Installations Certi cate No ANZEx 09 3000X Nonincendive Type n application Ex n Marking Code Ex n IIC T6...

Page 11: ...D for 2mm 0 8 in Dia Phone Tip Plug Used in FA3 FA4 FA8 FA10 FA11 and FA12 IPT CURRENT PRESSURE TRANSMITTER IN IN SPAN ZERO 39mm 1 54 in 2 Zero Adj Span Adj T T Pneumatic Test Jack Used in options FA3...

Page 12: ...ibed in the Maintenance section Operation Reverse output operation Once adjusted and installed the IPT2 operates unattended except for occasional cleaning of the air supply lters If a malfunction is i...

Page 13: ...ly and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall no...

Reviews: