Moore Industries IPT2 User Manual Download Page 5

IPT

  

2

 

The Interface Solution Experts 

5

Instrument Air and 
Filtration Information

Note:

For optimum performance, the selection and 

use of a good quality air fi ltration system is 

essential.  Most users fi nd that it is much less 

expensive and troublesome to design a system 

that includes good air fi ltration than deal with 

downtime and repairs later.  

A clean, dry air supply is important to assure the 
maximum service life of an IPT

2

.  Good air quality in-

volves removing solids, oil and water from the air after 
compression.  The cleaner the air, the longer the time 
before servicing is needed.

Oversizing elements avoids performance abberations 
and reduces maintenance time.  Redundancy should 
be used where possible to avoid shutdown during 
maintenance.  

Solids:  Random solid dirt, such as pipe scale and rust, 
is rarely a problem in compressed air instrument sys-
tems.  A good fi lter removes these solids.  However, if 
there is a desiccant dryer in the line, a high-effi  ciency 
sub-micron fi lter is recommended to remove the highly 
abrasive sub-micron particles produced by the dryer.

Liquid Oil:  Liquid oil is the most common problem in 
compressed air instrument systems.  A coalescing fi lter 
removes sub-micron liquid droplets from the air, and is 
usually supplied with an automatic drain.
 
A coalescing fi lter works by trapping oil and water 
droplets in a bed of microfi bers.  The droplets run 
together at fi ber cross-over points, form large liquid 
drops, and are forced by air fl ow to a drain.  A fi lter 
system consisting of a general purpose fi rst-stage fi lter 
(about 5 micron) and a high-effi  ciency coalescing fi nal 
fi lter is recommended to obtain contaminant-free air.

The exact location of the fi rst-stage fi lter is not im-
portant;  it can be located just ahead of each fi nal 
fi lter, or a single fi rst-stage fi lter can be located on a 
main line to protect a number of fi nal fi lters on branch 
lines.  Each fi nal fi lter (coalescing) should be located 
just ahead of each pressure regulator.  In a new plant 
installation, an oilless compressor may be used to 
eliminate this problem.

Water:  The amount of water in an air system 
depends on temperature, pressure and the relative 
humidity of the air.

Suffi  cient water must be removed to lower the dew 
point of the air to a temperature below ambient.  The 
dew point (at line pressure) is expressed as the tem-
perature at which any moisture in the system begins to 
condense.  

Water may be removed using a number of techniques, 
including coalescing fi lters, refrigeration dryers and 
desiccant dryers.  In addition, a variety of combina-
tions and modular systems may be used for special 
circumstances.

Care must be taken in the selection and location of  
the fi lter, because cooling downstream of the fi lter can 
cause more condensation of water.  A coalescing fi lter 
should be installed immediately upstream of the pres-
sure regulator.  This type of fi lter removes most of the 
water before the air enters the regulator.

For systems subjected to freezing temperatures, the 
portion of the system that runs outdoors should have a 
dryer installed.  The dryer reduces the dew point below 
the lowest expected outdoor temperature.  A desic-
cant dryer is used with a coalescing fi lter upstream to 
keep the desiccant dryer from being damaged by oil or 
overloaded with excessive condensed water.   Another 
high-effi  ciency coalescing fi lter is recommended down-
stream of the dryer, to remove the desiccant particles.

ISA Specifi cations:  The Instrument Society of America 
standard ISA-S73, 1975 (ANSI MC11.1-1975) covers 
the air quality requirements for instrument grade air for 
use in pneumatic installations.  

The dew point in outdoor installations must be at least 
7.8°C (18°F) below the minimum local ambient tem-
perature.  For indoor installations,  the dew point must 
be at least 7.8°C (18°F) below the minimum interior 
temperature or 2°C (35°F), whichever is greater.  
Although the ISA standard calls for a 35°F dew point, 
this is often unnecessary indoors, and may be unsatis-
factory outdoors under freezing conditions.

Filters that exceed the ISA specifi cation provide very 
inexpensive protection.  Although the ISA specifi cation 
calls for particle size not to exceed 3 microns and oil 
content not to exceed 1ppm, most fi lter manufacturers 
supply a line of coalescing fi lters that remove particles 
down to sub-micron sizes (often 0.01 micron) while 
also removing oil to below ISA 1ppm specifi cation 
(often to 0.01ppm).

Summary of Contents for IPT2

Page 1: ...IPT2 IPT 2 July 2016 170 730 00G Current to Pressure I P Transmitter All product names are registered trademarks of their respective companies Current to Pressure I P Transmitter...

Page 2: ...Information 5 Application Information 6 Calibration 7 Adjustments 7 Calibration Equipment 7 Test Jacks 8 Calibration Setup 8 Calibration Procedure 8 Installation 9 Mounting 9 Installation in Hazardou...

Page 3: ...r documentation is missing this number is used to identify equipment characteristics The model number for the IPT2 is located on a label on the side of the unit Serial Number Moore Industries maintain...

Page 4: ...FA11 FA12 See Table 1 for more information Housing DIN Aluminum DIN style housing assembly WTI Rain proof as de ned by NEMA 3R FA7 or FA8 required WTIP Rain proof as de ned by NEMA 3R with plate and...

Page 5: ...on temperature pressure and the relative humidity of the air Su cient water must be removed to lower the dew point of the air to a temperature below ambient The dew point at line pressure is expressed...

Page 6: ...on to prevent oil contamination of the desiccant as well as downstream ltration to prevent desiccant nes from introducing new contamination The service life of an IPT2 is directly proportional to the...

Page 7: ...he wiper stop Usually a slight change can be felt when the clutch is at the end of a range i e it is slipping However if this change is not felt either end can be reached by turning the shaft 15 turns...

Page 8: ...illustration of a typical calibration setup including optional equipment To check or calibrate the IPT2 connect the unit as shown in this illustration Calibration Procedure There are two options show...

Page 9: ...the unit into place until the retaining lever snaps up ush be neath the handle To remove an IPT2 press down on the retaining lever and lift the unit out by the handle Note Check valves in the headers...

Page 10: ...be used when the IPT2 is installed in a Class I Division 2 location Australia New Zealand ANZEx Installations Certi cate No ANZEx 09 3000X Nonincendive Type n application Ex n Marking Code Ex n IIC T6...

Page 11: ...D for 2mm 0 8 in Dia Phone Tip Plug Used in FA3 FA4 FA8 FA10 FA11 and FA12 IPT CURRENT PRESSURE TRANSMITTER IN IN SPAN ZERO 39mm 1 54 in 2 Zero Adj Span Adj T T Pneumatic Test Jack Used in options FA3...

Page 12: ...ibed in the Maintenance section Operation Reverse output operation Once adjusted and installed the IPT2 operates unattended except for occasional cleaning of the air supply lters If a malfunction is i...

Page 13: ...ly and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall no...

Reviews: