is a compact, closed-loop, 2-wire current-to-
pressure transmitter that converts a standard process
current signal to a pneumatic output. In its compact
aluminum housing, the IPT
2
snaps onto standard
mounting rails or onto a Moore Industries RIR or SIR.
Because of the low dynamic mass of the transducer
element, the unit can be mounted in any position and
is also insensitive to shock and vibration.
Individual IPT
2
s consist of two parts: the transmitter
section and an interlocking pneumatic mounting
Introduction
This is the users’ manual for Moore Industries’
advanced current-to-pressure transmitter, the IPT
2
. It
contains all of the information needed to confi gure,
install, operate, and maintain the IPT
2
.
The following guidelines are used in this manual:
WARNING - Hazardous procedure or condition that
could injure the operator.
Caution - Hazardous procedure or condition that
could damage or destroy the unit.
Note - Information that is helpful for a procedure,
condition, or operation of the unit.
block, which snaps onto a rail. Units that are ordered
without a mounting block will clip onto an RIR or
SIR, which supplies air to each unit using only one
pneumatic supply pipe. Both mounting blocks
and supply headers contain self-sealing valves.
Therefore, the IPT
2
can be removed and replaced
without disturbing the pneumatic connections or
causing accidental venting of the supply or output air.
Operation can be monitored or calibration performed
by using the electrical input and optional pneumatic
output test jacks. A red LED display, which indicates
the presence of an electrical input signal, is also
standard.
Table 1 contains the IPT
2
equipment specifi cations,
including inputs, outputs, power requirements, and
performance characteristics.
Model Number. The IPT
2
model number describes
the equipment type, functional characteristics,
operating parameters, any options ordered, and unit
housing. If all other documentation is missing, this
number is used to identify equipment characteristics.
The model number for the IPT
2
is located on a label
on the side of the unit.
Serial Number. Moore Industries maintains a
complete history on every unit it sells and services.
This information is keyed to the serial number. When
service information is required on the IPT
2
, it is
necessary to provide the factory with this number.
The serial number is located on the side of the unit.
Accuracy:
<±0.25% of span
including the combined eff ect
of linearity, hysteresis, and
repeatability (between 0.5
and 3psi output, error will not
exceed ±1.0% of span)
Stability:
Not to degrade
from stated accuracy for six
months
Step Response:
<0.2 sec-
onds into 100 M.L. load
(6 cubic inches) at 90%
output span
Supply Pressure Eff ect:
Negligible from 20-40psig,
steady pressure
Air Consumption:
0.08 SCFM, typical
(0.18 kg/hr)
Air Capacity:
Minimum 2.0 SCFM
Air Supply:
Instrument air
only, 20-40psig. (Must be 5
psig greater than maximum
output)
Voltage Drop:
7.5V, maximum (5V maxi-
mum without LED)
Mounting Position Eff ect:
Negligible, unit can be
mounted in any position
Shock and Vibration Eff ect:
0.25%/G or better over
5-15Hz; meets SAMA PMC
31.3
Operating & Storage Range:
-40°C to +80°C
-40°F to +176°F
Ambient Temperature Eff ect:
<±0.025% of span/°C, max
from 0°C to 50°C;
<±0.1% of span/°C, max.
RFI/EMI Eff ect:
<±0.1% of span change at
50V/m @ 20-1000MHz.
Zero & Span:
Screw adjusts
zero or span by ±10% mini-
mum, non-interactive
Performance
Specifi cations
Electrical:
Removable front-mounted
terminal blocks, 22-14 AWG
Pneumatic:
1/8-inch NPT
female for both supply air
and output air on units with
optional mounting block.
Pneumatic Test Jacks:
Monitors output pressure
during calibration
Current Test Jacks:
Input
current test jacks (lT,
–T) for calibration; accepts
2mm (0.08 in) dia x 13mm
(.50 in) long phone tip plugs
(handles should be less than
8mm (0.32 in) in diameter)
LED:
Red light-emitting
diode indicates presence and
intensity of electrical input
signal.
438g (15.6 oz)
Performance
(Continued)
Ambient
Conditions
Adjustments
Connections
Adjustments
Connections
(Continued)
Indicators
Weight