Moore Industries IPT2 User Manual Download Page 12

IPT

  

2

12 

The Interface Solution Experts

1.   Remove the IPT

2

 from the mounting block by 

pressing down on the locking lever and pulling 
straight out to disengage the pneumatic fi ttings.   

2.  To remove the supply air fi lter screen, fi rst slide 

the nozzle retainer clip to the right and then pull 
the nozzle out of the main body.  

3.  Remove the fi lter screen and fl ush with TCE and 

air dry before reinstalling.  

4.  Slide the nozzle back into the main body.

Troubleshooting

Many components of the IPT

2

 have been thermally 

aged, tested, and selected using a computer-aided 
design program.  This usually makes fi eld repair 
unnecessary.  It is therefore recommended that any 
unit found to be performing below specifi cations 
be returned to the factory in accordance with the 
instructions found on the back cover of this manual.      

If a problem is suspected with the IPT

2

,  review the 

following steps:

1.  Make sure that all connections are clean and 

tight.

2.  Verify that bench instruments used to take 

measurements have the proper range and 
accuracy and are currently certifi ed.

3.  Check that the bleed-air port (located in a slot on 

the right side panel) is not restricted.

4.  Using a test jumper, connect one end to the 

metal case and the other end to an "IN" terminal 
while observing the output pressure.  The output 
pressure should not change.

5.  If a change in the relationship between the input 

and the output occurs, try to correct it by re-
adjusting the Zero and Span controls.

6.  If the response time lengthens or the span drops, 

this may indicate a blockage due to air supply 
contamination.  Clean the orifi ce and the supply 
air fi lter as described in the Maintenance section.

Operation

Reverse output operation: 

Once adjusted and installed, the IPT

2

 operates 

unattended, except for occasional cleaning of the air 
supply fi lters.  

If a malfunction is isolated to the IPT

2

, refer to the 

Troubleshooting section for recommendations.  A unit 
may become warm during operation, especially where 
the ambient temperature is elevated.  This is normal 
and should not be cause for alarm.

The high-performance line of I/P transmitters 
utilizes an internal feedback loop to ensure accurate 
operation. The feedback loop consists of an internal 
pressure transducer that samples the unit’s output 
pressure and compares it to the input signal. This 
allows the unit’s output to track the input signal. 

Since the feedback loop requires power to operate, 
when there is no input power to the unit, the 
pneumatic output will be shut off . Units that use 
mechanical positioning only, will typically still have a 
pneumatic output when power is removed. 

This is not an issue except for those users that rely on
this elevated output (18PSIG) to maintain a valve’s
position upon the unexpected loss of input signal 
(4-20mA). In such cases, the IPT

2

 reacts diff erently by 

shutting off  the pneumatic output.

Maintenance

After the IPT

2

 has been installed into the application, 

no maintenance is required.

However, the IPT

2

 is equipped with a plunger to clean 

the orifi ce.  To use the orifi ce-plunger, depress the 
plunger located on the side of the unit.  This pushes 
a stainless steel wire through the orifi ce and removes 
any particles lodged inside.  The output pressure will 
fl uctuate when the plunger is activated.

If the plunger does not fi x the problem, the supply 
air fi lter screen should be removed and fl ushed with 
trichloroethance (TCE) and then air dried before 
replacement.  Follow the directions below.

Summary of Contents for IPT2

Page 1: ...IPT2 IPT 2 July 2016 170 730 00G Current to Pressure I P Transmitter All product names are registered trademarks of their respective companies Current to Pressure I P Transmitter...

Page 2: ...Information 5 Application Information 6 Calibration 7 Adjustments 7 Calibration Equipment 7 Test Jacks 8 Calibration Setup 8 Calibration Procedure 8 Installation 9 Mounting 9 Installation in Hazardou...

Page 3: ...r documentation is missing this number is used to identify equipment characteristics The model number for the IPT2 is located on a label on the side of the unit Serial Number Moore Industries maintain...

Page 4: ...FA11 FA12 See Table 1 for more information Housing DIN Aluminum DIN style housing assembly WTI Rain proof as de ned by NEMA 3R FA7 or FA8 required WTIP Rain proof as de ned by NEMA 3R with plate and...

Page 5: ...on temperature pressure and the relative humidity of the air Su cient water must be removed to lower the dew point of the air to a temperature below ambient The dew point at line pressure is expressed...

Page 6: ...on to prevent oil contamination of the desiccant as well as downstream ltration to prevent desiccant nes from introducing new contamination The service life of an IPT2 is directly proportional to the...

Page 7: ...he wiper stop Usually a slight change can be felt when the clutch is at the end of a range i e it is slipping However if this change is not felt either end can be reached by turning the shaft 15 turns...

Page 8: ...illustration of a typical calibration setup including optional equipment To check or calibrate the IPT2 connect the unit as shown in this illustration Calibration Procedure There are two options show...

Page 9: ...the unit into place until the retaining lever snaps up ush be neath the handle To remove an IPT2 press down on the retaining lever and lift the unit out by the handle Note Check valves in the headers...

Page 10: ...be used when the IPT2 is installed in a Class I Division 2 location Australia New Zealand ANZEx Installations Certi cate No ANZEx 09 3000X Nonincendive Type n application Ex n Marking Code Ex n IIC T6...

Page 11: ...D for 2mm 0 8 in Dia Phone Tip Plug Used in FA3 FA4 FA8 FA10 FA11 and FA12 IPT CURRENT PRESSURE TRANSMITTER IN IN SPAN ZERO 39mm 1 54 in 2 Zero Adj Span Adj T T Pneumatic Test Jack Used in options FA3...

Page 12: ...ibed in the Maintenance section Operation Reverse output operation Once adjusted and installed the IPT2 operates unattended except for occasional cleaning of the air supply lters If a malfunction is i...

Page 13: ...ly and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall no...

Reviews: