background image

Page 20

Hotshot Gas Fireplace Insert

XG0511 - 150203

Appendix

Appendix: 

State of Massachusetts

Amendment

(Gas Fireplace / Equipment sold in the State of Massachusetts)

5.08: Modifications to NFPA-54, Chapter 10

 

(1) Revise NFPA-54 section 10.5.4.2

 

by adding a second exception as follows:

Existing chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manually reset device 

that will automatically shut off the gas to the burner in the event of a sustained back-draft

.

 

(2) Revise 10.8.3

 by 

adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, 

including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in 

the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 

 

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.

 

At the time of installation of the side wall horizontal vented gas fueled equip-

ment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor 

level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon 

monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled 

equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon 

monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with 

alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days 

to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm 

shall be installed.

 

2. APPROVED CARBON MONOXIDE DETECTORS.

 

Each carbon monoxide detector as required in accordance with the above provisions 

shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified. 

 

3. SIGNAGE.

 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet 

above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print 

size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

 

4. INSPECTION.

 The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, 

upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. 

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 

 

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the 

Board; and 

 

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or struc-

ture used in whole or in part for residential purposes.  

 

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED

. When the manufacturer of Product 

Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions 

provided by the manufacturer for installation of the equipment and the venting system shall include:

 

1. Detailed instructions for the installation of the venting system design or the venting system components; and

 

2. A complete parts list for the venting system design or venting system. 

 

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

. When the manufacturer of a Prod-

uct Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, 

the following requirements shall be satisfied by the manufacturer:

 

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and 

 

2. The “special venting systems”

 shall be Product Approved by the Board, and the instructions for that system shall include a parts list and 

detailed installation instructions. 

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for 

venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

 

(3) After NFPA-54 section 10.10.4.2

 add a new section 10.10.4.3 as follows:

When more than four gas appliances are to be vented through a common gas vent or common horizontal vent manifold, a plan of the proposed vent installation 

shall be submitted to the Inspector and the serving gas supplier for review and approval.

Extraction from: Massachusetts Rules and Regulations

5.00: Amendments To 2002 Edition Of ANSI Z223.1-NFPA-54

Summary of Contents for Hotshot DHS

Page 1: ...rature Strong magnetic field Optical radiation Non ionizing radiation Radiation Hazardous to the Environment Danger of harming your hands Irritant Cutting Watch your step Slippery floor High temperatures Glass hazard Danger of suffocation High voltage Toxic Flammable materials Corrosive Fork lift trucks Danger overhead crane Explosion risk Oxidising Danger of death Biohazard Laser Radiation Danger...

Page 2: ...s 6 Clearances 7 Installing the Gasline 7 Chimney Liner Installation 8 Face Plate Trim and Louvres Face Plate Installation 9 Lower Louvre Assembly 9 Face Plate Trim 9 Upper Louvre Assembly 10 Wiring for the Air Circulating Fan 11 Removing and Installing the Screen Door 12 Installing the Logset 13 Operation 14 15 Maintenance 16 17 Warranty 19 Appendix 20 ...

Page 3: ...n a masonry fireplace equipped with a double burner glowing embers and a six piece log set The Hotshot DHS is rated for Natural Gas or Propane at 25 000 BTU H 7 4 Kilowatts We strongly encourage you to read and carefully follow the instruc tions laid out in this Installation Operation and Maintenance Manual and retain it for your future reference Pay special attention to all cautions warnings and ...

Page 4: ...l etc It is imperativethat controlcompartments burnersand circulatingair passagewaysof the fireplace are kept clean NOTICE Installations in Canada must conform to the local codes or in the absence of local codes to the current version of Natural Gas and Propane Installation Code CSA B149 Electrical Installations must conform to the local codes or in the absence of local codes to the current versio...

Page 5: ...Page 5 Hotshot Gas Fireplace Insert XG0511 150203 Installation Rating Plate Sample LBL1205 V6 1 Stand Pilot Screen DEC06 2014 Teklynx LabelView Demo ...

Page 6: ...ions Figure 1b Deluxe Arched Faceplate dimensions Figure 1c Standard Faceplate dimensions 27 3 4 705 25 634 21 3 8 544 10 3 4 272 20 507 23 5 8 600 14 1 8 357 27 3 4 705 16 1 4 411 15 7 8 405 20 1 4 513 21 1 2 545 14 5 8 371 16 1 8 410 11 280 Top View Front View Side View Note Images are shown without screens for clar ity purposes However your fireplace should not be operated without proper instal...

Page 7: ...ssure testing of that system at test pressures in excess of 1 2 psig 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Figure 3 Gas line location Note After the gas line is connected each appliance con nection val...

Page 8: ...ssible into the fireplace open ing Reach inside the opening above the Hotshot and insert the vent connector into the slot at the back of the fireplace Push the connector slide back as far as it will go to secure the chimney liner in position See figure 5b Centre the Hotshot in the fireplace opening and connect the gas line See Figure 3 To install the face plate and louvres see Installing Face Plat...

Page 9: ...ep 2 Install the Lower Louvre Assembly Position the Lower Louvre Assembly as shown in Figure 7 Line up the screw holes on the hinge with the pilot holes on the front of the fireplace and attach using three screws The lower louvres should rotate freely allowing easy access to the Hotshot control compartment Step 3 Install the Face Plate Trim To assemble the face plate trim slide the top end of the ...

Page 10: ...the top rail and one screw into each of the side rails as shown in figure 8b To remove face plate or face plate trims simply reverse above procedures Figure 8b Installing the trim Figure 9a Installing the upper louvres Figure 9b Installing the upper louvres Raise the Upper Louvre over the heat deflector ensuring the heat deflector is positioned between the bottom and middle louvre Figure 9c Comple...

Page 11: ...SA must be grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 NOTE If any of the original wire supplied with the appliance is replaced it must be replaced with the same type or its equivalent Removing and Installing the Screen and Door Removing the screen and door Figure 11a Removing the screw covers G H N Motor Fuse Heat sensor ...

Page 12: ...lass cleaner such as Kel Kem or White off NOTICE Installing the screen and door 1 Push the door up along the front of the firebox until the top edge of the door frame is underneath the Hotshot hood Line up the screw holes in the door with the corresponding holes on the front of the fireplace and attach with the four screws 2 Place screen over door and line up screw holes 3 Attach with four screws ...

Page 13: ...the fireplace If the flame appears satisfactory replace the glass door and door cover Figure 12a Positioning for the top logs C and D Installing the Log Set Installing the Logs The double burner Hotshot is supplied with a six 6 piece fibre log set 1 Remove the door cover and the glass door Back log Left log Right log Front log Center logs Figure 12b Proper placement top view Back log Front log res...

Page 14: ...turned from PILOT to OFF unless knob is pushed in slightly Do not force Standing Continuous Pilot Ignition SIT NOVA 820 with American Flame Electronic Ignition For Your Safety READ BEFORE LIGHTING If you cannot reach your gas supplier call the Fire Depart ment C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repa...

Page 15: ...terclockwise Figure 13 Hi Lo Adjustment on the Hotshot inset s gas valve Fan Adjustment Turn the fan On Off Speed Control to On The Fan will turn on and off automatically depending on the appliance s temperature Adjust the fans speed by turning clockwise or counterclockwise See figure 13 WARNING Avoid contact with hot fireplace glass while adjusting burner Fan On Off Speed Control On Off Switch Fi...

Page 16: ...ny part of the control system and any gas control which has been under water Cleaning WARNING Do not attempt to clean glass when hot Do not clean glass with abrasive materials as any glass etch ing may cause premature glass failure When the fireplace is first activated there may be some smoking and a visible film may be left on the glass This is a normal condition and is the result of burning of p...

Page 17: ...lly slide the burner tray forward to remove You may need to disconnect the gas line to remove the burner 6 Carefully put the burner tray to the side Take care to not damage the pilot wires Figure 14b Figure 14c 7 Remove 10 screws holding down the fan cover access plate Figure 14d 8 Disconnect fan power Remove the screws holding down fan bracket 9 Reverse steps to reinstall Make sure to replace the...

Page 18: ... Check wall switch for proper con nection 3 Check high limit switch If your fireplace still does not operate correctly consult your dealer or the manufacturer All service and repairs should be performed by a qualified agency All spare parts and optional such as trim finishes and the wireless infrared remote control are available from your local dealer or the manufacturer Replacement Parts Standing...

Page 19: ...be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and understood that The Companies sole obligation and purchaser s exclusive remedy under ...

Page 20: ...t of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve th...

Page 21: ...Page 21 Hotshot Gas Fireplace Insert XG0511 150203 Notes ...

Page 22: ...Ferndale Washington TF 1 800 789 6236 FX 1 866 3000 0927 Langley British Columbia TF 1 800 378 3115 FX 1 604 607 6462 XG0511 150203 Gas Fireplace Insert Hotshot ...

Reviews: