14
Programmed Alarm Output (T3-11)
The output at T3-11 is similar to that
described for the horn in Table 7-1 except
that the Programmed Alarm output does
not respond to the # button on the keypad.
It only responds to alarm situations. The
output is a 24 Vdc signal.
Aux Alarm Output (T5-1, 2 and 3)
The Auxiliary Alarm output is a set of
Form-C dry relay contacts on T5-1, 2 and
3. The relay controlling these contacts is
activated continuously when:
a. The door switch input (T3-5 and T3-6)
indicates that the door is ajar, and
b. The Lock Switch Input (T3-7 and T3-8)
is open, and
c. The lock has not been released by either
the valid PIN or the Release Button.
The Auxiliary alarm Output contacts are
rated at 1A maximum.
If a lock monitoring switch will be
monitored remove the jumper from JP2. If
a lock monitoring switch will not be used,
verify that a jumper is installed on JP2
(JP2 shunts the lock switch input terminals
T3-6 and T3-7).